BACKFLOW PREVENTION ASSEMBLY TESTER EXAM 2024 EDITION, Exams of Water Resources Planning and Management

BACKFLOW PREVENTION ASSEMBLY TESTER EXAM 2024 EDITION Back flow prevention testing equipment should be accuracy verified at least every _______ - Correct Ans: ✔✔year A damaged or dirty disc or seat of an RPBA may account for ______ - Correct Ans: ✔✔A low first check differential

Typology: Exams

2024/2025

Available from 11/24/2024

Martin-Ray-1
Martin-Ray-1 🇺🇸

2.7K documents

1 / 10

Toggle sidebar

Related documents


Partial preview of the text

Download BACKFLOW PREVENTION ASSEMBLY TESTER EXAM 2024 EDITION and more Exams Water Resources Planning and Management in PDF only on Docsity!

BACKFLOW PREVENTION ASSEMBLY

TESTER EXAM 2024 EDITION

Back flow prevention testing equipment should be accuracy verified at least every _______ - Correct Ans: ✔✔year A damaged or dirty disc or seat of an RPBA may account for ______ - Correct Ans: ✔✔A low first check differential Inconsistent, erratic test results found when testing a RPBA means that

  • Correct Ans: ✔✔There is air in the assembly If you get "impossible" test kit readings when testing an assembly - Correct Ans: ✔✔First check to see if hoses are hooked up to the right test ports When testing a PVB, the air inlet valve does not open as the gauge drops to 0 - Correct Ans: ✔✔The air inlet disc is stuck to the seat in the up position To continue practicing the profession, grade 6 operators must complete CE before the expiration date of every ________ year renewal period - Correct Ans: ✔✔ 3

Nebraska regulations require that backflow prevention assemblies be tested ________ - Correct Ans: ✔✔Once each year If an RPBA dips continually from the vent, the problem could be ________ - Correct Ans: ✔✔The #1 check valve is faulty High hazard locations according to the NDHSS DPH regulations include _______ - Correct Ans: ✔✔Truck (water) loading stations Which statement is correct according to the Nebraska regulations - Correct Ans: ✔✔Annual testing is required for RPBAs` If the relief valve fails to open while testing a RPBA, the problem could be - Correct Ans: ✔✔A fouled sensing line Water leakage over the top of an AVB may be cause by _________ - Correct Ans: ✔✔A damaged or corroded guide A leaky check valve of a DCVA could be due to _________ - Correct Ans: ✔✔The guide members hanging up A problem sometimes after repairing a DCVA is _______ - Correct Ans: ✔✔A noisy vibration

A differential pressure relief vlave on an RPBA that failed after testing can have two _________ which must be inspected - Correct Ans: ✔✔Diaphragms When you have re-assembled an RPBA, __________ to detertime if the relief valve has closed - Correct Ans: ✔✔Stick your fingers into the discharge port The #2 test port of a DCVA is located - Correct Ans: ✔✔Between the #1 shutoff valve and the #1 check valve If after repairing a DCVA the device still does not test out "ok" - Correct Ans: ✔✔The device should be disassembled and the check valve seats re-cleaned The _____ found in the second check valve of an RPBA is different than in the first - Correct Ans: ✔✔Spring The backflow prevention assembly test report is required to be completed using the forms (if any) provided by the PWS having jurisidiction because _____ - Correct Ans: ✔✔The grade VI operator is actually a specialized (limited) PWS operator licensed work under the rules and regulations of a PWS

State drinking water regulations require fire protection sprinkler systems to comply with ______ - Correct Ans: ✔✔AWWA Manual M What is that Duke, Midwest, Watts and Barton all have in common - Correct Ans: ✔✔They all sell testing equipment for testing RPBAs When testing a PVB, the test gauge must be - Correct Ans: ✔✔At the same height of the assembly The air inlet valve of a PVB device - Correct Ans: ✔✔Is held open until sufficient pressure is applied inside the PVB Which method of protecting against high hazard back siphonage is the best - Correct Ans: ✔✔Air gap After a backflow prevention assembly has been tested, a copy of the certified results is provided to the ______ - Correct Ans: ✔✔Owner State regulations place the responsibility on the _______ for records of locations, type of backflow preventers, and record of repairs of back flow preventers - Correct Ans: ✔✔Consumer

When reassembling components after repairs are made to a backflow prevention device or assembly - Correct Ans: ✔✔An approved nontoxic lubricant may be used In order to be certain which device/assembly you are about to test, you should - Correct Ans: ✔✔Check and record the make, model, and serial number A water column 55 1./2" high will create a pressure of _______ psi at the bottom - Correct Ans: ✔✔ 2 To smooth a lightyly scratched check valve seat of a PVB, the best choice would be to use - Correct Ans: ✔✔Sand cloth NDHHS DPH regulations require that fire protection backflow prevention assemblies be tested - Correct Ans: ✔✔According to the Nebraska state fire marshal regulations When a DCVA whines or growls, it is probably due to - Correct Ans: ✔✔Air trapped in the covers The relief valve of a RPBA must be able to operate - Correct Ans: ✔✔To maintain the zone between the two check valves at least 2 psi less than the supply pressure

DCVA and RPBA installations require ________ minimum clearance below the assembly and a maximum of _________ above ground, work floor, or permanent working platform - Correct Ans: ✔✔1' 5' A consumer claims his DCVA must be causing a steady reduction of pressure over the last 6 months. Your option might be to - Correct Ans: ✔✔Replace the service line because its probably full of scale When testing the #2 check valve on a RPBA against reverse of flow, install the high hose on the _______ test cock - Correct Ans: ✔✔# Line pressure fluctuation can cause problems when testing backflow prevention assemblies, if this is the case, an experienced grade VI water operator will likely - Correct Ans: ✔✔Schedule testing when pressure are more steady and take the highest reading A differential pressure gauge described in the Nebraska standards for testing backflow preventers should be designed for ________ - Correct Ans: ✔✔ 0 - 15 PSID A water heater thermal expansion control is required by ______ when a containment device/assembly is installed - Correct Ans: ✔✔some plumbing codes

The _______ test port is located between the two check valves on a RPBA - Correct Ans: ✔✔# The RPBA and DCVA must be installed - Correct Ans: ✔✔At least 12" above ground or work floor Atmospheric pressure at sea level is about ______ psi - Correct Ans: ✔✔14. When a RPBA relief valve assembly is put back into the body, a good way to check it for proper movement is to - Correct Ans: ✔✔Simply push on the diaphragm plate When a person is licensed to test backflow preventers, he/she is also licensed to - Correct Ans: ✔✔repair them A PWS practicing containment to protect the water system from cross connections encounters an unprotected tap between the meter and the backflow prevention assembly. In this situation.... - Correct Ans: ✔✔The installation should not be approved

Threaded hose bib faucets are potential cross connections, but technically can be brought into compliance by... - Correct Ans: ✔✔Filing of the threads so that a hose cannot be attached To be certain that a backflow preventer is approved for the particular installation... - Correct Ans: ✔✔Contact the PWS Although not recommended because of the high risk of contamination, Nebraska standards describe mercury manometers can be used to calibrate - Correct Ans: ✔✔Differential pressure gauges Nebraska standards require that an RPBA have two independently operating check valves with a ______ relief valve located between the check valves - Correct Ans: ✔✔Mechanically independent Nebraska standards require that the DCVA must have to be tightly closing _______ shut off valves four _______ test ports - Correct Ans: ✔✔Resilient seated Resilient seated For all backflow assemblies.... - Correct Ans: ✔✔There is no test port down stream from shut off valve #

For the flow rates specified in the Nebraska standards, the maximum pressure loss allowed for all sizes of DCVA is..... - Correct Ans: ✔✔ 10 psi If an RPBA contiunually drips or drains under full flow conditions - Correct Ans: ✔✔The #2 check valve is fouled When a residential property has a backflow-prevention device/assembly installed on the service line the best means to control thermal expansion is with a - Correct Ans: ✔✔Thermal expansion tank According to the Nebraska regulations what is the minimum acceptable air gap for a 2" pipe located 1" from the wall - Correct Ans: ✔✔6" The RPBA must have a provision to drain away at least _____ times the rated flow of the assembly - Correct Ans: ✔✔ 4 When velocity of the water flowing in a service pipe increases, the pressure available at the consumers tap _________ - Correct Ans: ✔✔Decreases The second check valve of a DCVA has become distorted. What could have caused this? - Correct Ans: ✔✔Water hammer

The RPBA #1 check valve is ___________ - Correct Ans: ✔✔A heavier spring than used in the #2 check valve The check valve spring of a PVB ________ - Correct Ans: ✔✔Closes the check valve The _____ test cock of an RPBA is located on the inlet side of the assembly - Correct Ans: ✔✔# If a 10" RPBA doesnt test properly - Correct Ans: ✔✔Check to see if the downstream gate valve is leaking