Partial preview of the text
Download S-12 CITYWIDE SPRINKLER SYSTEMS, S12 sprinkler test |193 Questions and answers already gra and more Exams Engineering in PDF only on Docsity!
THE IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO DETERMINE QUALIFICATIONS. - ¥JOWNER RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A MIN. OF YEARS. - V¥3 THE BUILDING OWNER SHALL ASSIGN A(N) TO COMPLY WITH REQUIREMENTS. - V¥ VIMPAIRMENT COORDINATOR REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE. - V/V 1 SHUTDOWNS AFFECTING MORE THAN FLOOR(S) ARE CONSIDERED UNPLANNED OUT OF SERVICE CONDITIONS. - V1 NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO SERVICE WITHIN HOURS. - VV8 FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY REPORT CONDITION TO THE ANDTHE FIRE DEPT. - /YOWNER OF THE BUILDING IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT. - //30 WHAT DOES "OOS" STAND FOR? - V YOUT OF SERVICE OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING AT FIRE DEPT. CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER - // TAGS A SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND ANY SECTIONAL VALVES. - // MASTER FIRE SUPPRESSION PIPING CONTRACTOR SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW PRESSURES BEFORE AND AFTER. - / /DRAIN TEST RESULTS GREEN TAGS INDICATE THAT .- VV NO IMPAIRMENT WAS FOUND GREEN TAGS WILL BE PLACED ON THE .- VV MAIN CONTROL VALVE SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A TAG PLACED ON THE MAIN CONTROL VALVE. - VV RED A DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE SYSTEM IS FULLY OUT OF SERVICE. - / WHITE A CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE AND SPRINKLER SYSTEMS. - J /MASTER FIRE SUPPRESSION PIPING CONTRACTOR (MFSPC) A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES WITH SPRINKLER HEADS OR LESS. - /¥30 ABOUT PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED WHEN SPRINKLERS ARE INSTALLED. - / 96 WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF TO PREVENT THE SYSTEM FROM FREEZING. - /V40 FAHRENHEIT VALVES ARE NO LONGER PERMITTED TO BE INSTALLED. - / /COLD WEATHER SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM CANNOT BE HEATED TO PREVENT FREEZING. - VV DRY PIPE THE DROP IN CAUSES A SPECIAL DRY PIPE VALVE TO OPEN. - / AIR PRESSURE IN BUILDINGS WHERE LIFE HAZARD IS HIGH (SCHOOLS, HOSPITALS) THE ALARM IS TRANSMITTED DIRECTLY TO THE .- V VFIRE DEPARTMENT DRY PIPE VALVES ARE OF A DESIGN. - V/ CLAPPER DRY PIPE VALVES ARE USUALLY SETAT___ PSI ABOVE THE NORMAL TRIP LEVEL. - V ¥15-20 AN ACCELERATOR AND EXHAUSTER ARE USED TO THE TIME TO ALLOW WATER INTO THE SYSTEM. - ¥¥ REDUCE BOTH ACCLERATOR AND EXHAUSTER ARE ACTIVATED WHEN A DROP OF PSI IS DETECTED IN THE SYSTEM. - V2 IN A PREACTION SYSTEM, THE IS OPENED BEFORE THE SPRINKLER HEADS. - V¥ VPREACTION VALVE PREACTION SYSTEM ALARMS ARE GIVEN AS SOON AS THE IS OPENED. - /V VALVE THREE DEVICES USED TO TRIP PREACTION VALVES ARE FIXED TEMP DEVICES, RATE DEVICES, AND. DEVICES. - // COMBINATION THE FEATURE SHUTS OFF WATER WHEN THE FIRE IS EXTINGUISHED AND TURNS ON AGAIN IF THE FIRE REKINDLES. - / /RECYCLING THE IN THE DELUGE SYSTEM ARE OPEN AT ALL TIMES. - V/V SPRINKLER HEADS SYSTEMS ARE USUALLY FOUND IN BASEMENTS OR OTHER DIFFICULT TO REACH AREAS. - VJ PERFORATED PIPE IF THE SPRINKLER SYS. IS SUPPLIED FROM PUBLIC WATER MAIN, THE CONTROL VALVE SIGN MAY READ .- V/"SHUTOFF FOR SPRINKLER SYS. LOCATED 6 FEET FROM THIS SIGN" GATE VALVES OF THE NON-INDICATING TYPE ARE CALLED .- ¥ /CURB VALVES IN AN OUTSIDE STEM AND YOLK VALVE (OS&Y), VALVE POSITION IS INDICATED BY THE POSITION OF THE .- V/STEM ON A POST INDICATOR VALVE (PIV), THE POSITION OF THE VALVE IS SHOWN THROUGH A - VV TELLTALE FDNY CONNECTIONS TO AUTOMATIC SPRINKLER SYSTEMS SHALL BE PAINTED 32 VJ/GREEN FDNY CONNECTIONS TO NON-AUTOMATIC SPRINKLER SYSTEMS SHALL BE PAINTED - VVSILVER FDNY CONNECTIONS TO STANDPIPE SYSTEMS SHALL BE PAINTED .- VVRED FDNY CONNECTIONS TO A COMBINED STANDPIPE/SPRINKLER SYSTEM SHALL BE PAINTED - VVYELLOW FDNY CONNECTIONS SHALL BE FITTED WITH A LOWER CHECK VALVE. THIS WILL PREVENT OF WATER. - // BACKFLOW. PRESSURE TANKS SHOULD BE KEPT FULL AND BE MAINTAINED AT OR ABOVE PSIi- VV2/3,75 ARE DESIGNED TO TAKE WATER FROM A SUPPLY AND DISCHARGE IT UNDER PRESSURE. - vJFIRE PUMPS AUTOMATIC FIRE PUMPS ARE USUALLY NEEDED WHERE A MAY OCCUR IMMEDIATELY. - V¥ VHIGH WATER DEMAND WATER ALARMS SERVE AS FIRE EXTINGUISHING SYSTEMS AND SERVE AS A(N) - v¥ VAUTOMATIC FIRE ALARM. SPRINKLER SYSTEMS ARE REQUIRED TO HAVE AN APPROVED MOTOR GONG, BELL, HORN, OR - VVSIREN SPRINKLERS MANUFACTURED AFTER 1/1/2000 ARE REQUIRED TO HAVE A .- Vv VSPRINKLER IDENTIFICATION NUMBER (SIN) SPRINKLERS HAVE BEEN RECALLED. - /VCYCLING SPRINKLER HEADS EXPOSED TO CONDITIONS ARE OFTEN COVERED WITH A COAT OF WAX, OR LEAD. - V /CORROSIVE THE MAXIMUM GROSS CAPACITY OF PRESSURE TANKS IS GALLONS. - ¥V9000 PRIMARY WATER PRESSURE TANKS SHALL BE EQUIPPED WITH TWO .- VV HIGH AND LOW ALARM SYSTEMS PRESSURE TANKS MAY BE SUPERVISED BY AN APPROVED COMPANY WHICH MONITORS THE ENTIRE SPRINKLER SYSTEM. - // CENTRAL STATION TANKS ARE MADE OF WOOD, STEEL, OR CONCRETE. - / GRAVITY GRAVITY TANKS SHOULD BE AT LEAST FEET ABOVE THE HIGHEST LINE OF SPRINKLER HEADS. - VV25 FOR EVERY 1 FOOT THE TANK IS ABOVE THE DISCHARGE OUTLET PS| OF PRESSURE IS GENERATED. - V V0.433 AUTOMATIC FILL PUMPS FILL THE TANK AT A RATE OF GPM OR MORE. - VV65 THE TURN ONTHE FILL PUMP WHEN THE WATER IN THE TANK IS TOO LOW. - /V FLOATS SOME METHODS TO PREVENT ICE INSIDE A GRAVITY TANK ARE ------------------ v¥ VCIRCULATED HOT WATER, STEAM, STEAM COILS, AND SUN HEAT 10 THE MAIN REASON A SPRINKLER SYS. SUPPLIED BY A GRAVITY TANK FAILS IS .-¥/NOT ENOUGH WATER IN THE TANK THE PUMP IS THE STANDARD PUMP CURRENTLY USED IN FIRE PROTECTION SYSTEMS. - ¥V CENTRIFUGAL THE WATER AVAILABLE TO THE CENTRIFUGAL PUMP MUST ALWAYS BE .- J JUNDER PRESSURE CENTRIFUGAL PUMPS ARE CAPABLE OF DISCHARGING WATER FROM TO GPM. - V¥25, 5000 A VERTICAL TURBINE PUMP IS USED TO DRAW WATER FROM A WELL TO --VVFILLA STORAGE TANK. MUD, GRAVEL, AND LEAVES MAY CAUSE DAMAGE TO THE .- ¥VPUMP WHEN ARE INSTALLED, THEY ARE USUALLY USED IN COMBINATION WITH A GRAVITY TANK OR A PRESSURE TANK. - VW MANUALLY ACTIVATED PUMPS COF HOLDERS SHOULD MANUALLY ACTIVATE THE FIRE PUMPS IAW = v¥ VMANUFACTURER INSTRUCTIONS REMOTE PUSHBUTTONS ARE USED TO THE PUMP ONLY. - / /START 11 FOR PIPE OTHER THAN 1-1/4, THE MAXIMUM DISTANCE BETWEEN HANGERS |S FEET. - VvV15 CPVC PIPE HANGER SPACE FOR 3/4 INCH PIPE IS .-VJS5FT6IN CPVC PIPE HANGER SPACE FOR 3 INCH PIPE IS FEET.- V¥V10 THE DISTANCE FROM A HANGER ASSEMBLY TO THE CENTERLINE OF A SPRINKLER HEAD SHALL NOT BE LESS THAN -=--=-=-==-=-==-=-—= J V3 INCHES SYSTEMS ABOVE PS] HAVE DIFFERENT SUPPORT REQUIREMENTS. - V/V 100 NYC BUILDING CODE REQUIRES SWAY BRACING FOR SPRINKLER SYS. INSTALLED AFTER 3 V¥V1998 MINIMUM SIZE HANGER RODS FOR PIPE DIAMETER UP TO 4 INCHES: VV3/8 MINIMUM SIZE HANGER RODS FOR PIPE DIAMETER OF 5-8 INCHES: ------=---=----------=- VV1/2 MINIMUM SIZE HANGER RODS FOR PIPE DIAMETER OF 10-12 INCHES: ------------=--=------ VV5/8 THE INSIDE OF PRESSURE TANKS SHALL BE INSPECTED CAREFULLY EVERY YEARS. - / V3 13 WHEN INSPECTING PRESSURE TANKS, THE COMPRESSOR SHALL BE CAPABLE OF PRESSURIZING TO PSI WITHIN 3 HOURS OR LESS. - /V75 PUMPS SHOULD BE ACTIVATED EACH WEEK AND RUN FOR MINUTES IN ACCORDANCE TO THE MANUFACTURERS SPECIFICATIONS. - VV 10 INSTALLATIONS THAT DON'T APPEAR CORRECT INCLUDE SPRINKLER HEADS LOCATED MORE THAN INCHES BELOW THE CEILING. - VV 22 THE PRESENCE OF OBSTRUCTIONS IN SPRINKLER SYSTEMS SHALL BE CHECKED EVERY YEARS. -VVFIVE WHEN TUBERCULES AND SLIME ARE FOUND THEY SHALL BE TESTED FOR ae VJ MICROBIOLOGICALLY INFLUENCED CORROSION fire department connection - VV normally on exterior of building... FDNY can pump supplemental water into the sprinkler system, standpipe, or other system furnishing water for fire extinguishment to supplement existing water supplies. system control valve - / Vvalve controlling flow to water-based fire protection systems. fire command center - V /Designated room or area ina structure where the status of the fire detection, alarm, and protection systems is displayed and the systems can be manually controlled. 14 Early suppresion fast response sprinklers - / /fast response sprinkler that is listed for its capability to provide fire suppression of specific high challenge fire hazards extra large orifice sprinklers - / /= or > 1 inch less pressure to achieve a given discharge density extended coverage sprinkler - VV 400 max square feet discharge 20 foot by 20 foot spacing between sprinklers fire pump - / Va provider of liquid flow and pressure dedicated to fire protection. A fire pump is a part of a fire sprinklers system water supply and can be powered by electric, diesel or steam. connected to public water source or tank. provides higher pressure to sprinkler system Glass bulb sprinkler - / /operated by heat breaking a glass bulb filled with a non freezing liquid with diameters that vary form 3 mm for quick response to 5 mm for standard response hose valve - V ¥valve to additional hose connection hydraulic placard - V Vsign attached to a hydraulically calculated sprinkler system indicating the design density, required gallons per minute and pressure for the system to operate properly hydraulically calculated systems - Y V method of sizing auto sprinkler piping using a prescribed amount of water to be distributed over a specific area. 16 impairment coordinator - / Vin charge of safety during out of service systems intermediate level sprinkler - VV sprinkler equipped with integral shields to protect the operating elemtn form discharge from sprinklers installed at higher elevations large orifice sprinkler - / /sprinkler head with orifice size equal or greater than 3/4 and less than 1 inch listed device - VVA fire protection component that has been tested to perform under parameters specified for its use by a nationally recognized testing agency. Underwriter's Laboratory (UL) and Factory Mutual (FM) are the two most common. Master Pressure Reducing Valve - ¥ VA pressure reducing valve installed to regulate pressures in an entire fire protection system and/or standpipe system zone. Main Drain - V /The primary drain connection located on the system riser and also utilized as a flow test connection. Microbiologically Influenced Corrosion (MIC) - // Corrosion caused by the presence of microbes in the water supply that over time attack the interior of metallic piping and cause leaks, pitting, and blockages. Conventional Sprinkler - /WA sprinkler that directs 40% to 60% of the water initially ina downward direction and is designed to be installed with the deflector in either the upright or pendent position. Pendent Sprinkler - / VA sprinkler designed to be installed in such a way that the water stream is directed downward against the deflector. 17 Quick Response Sprinkler Head - /WA sprinkler having a fusible link with a response time index (RTI) of 50 or less. Recessed Sprinkler - / WA sprinkler in which all or part of the body, other than the shank thread, is mounted above the ceiling. Residential Sprinkler - / WA type of fast response sprinkler that has been specifically tested to enhance survivability in the room of fire origin and listed for use in dwelling units. Response Time Index (RTI) - YW A measurement of the thermal sensitivity of a sprinkler head expressed in (meters-seconds) 1/2. Supervisory signal - / VA signal indicating the need for action or the use of such device in connection with the supervision of fire alarm systems or the maintenance features of related systems. Small orifice sprinklers - /V/A sprinkler head with and orifice size smaller than 1/2" Solder Link Sprinkler - //A sprinkler operated by the melting of a metal link, they vary in size and configuration for quick response and standard response sprinklers. The smaller the size of the link, the faster the sprinkler operates. Spray Sprinkler - //A type of sprinkler listed for its capability to provide fire control for a wide range of fire hazards. The most commonly used sprinkler since 1953. 19 Standard Response Sprinkler Head - VA sprinkler having a fusible link with a response time index (RTI) of 80 or more. Supervisory signal-initiating device - / VAn initiating device, such as a valve supervisory switch, that triggers a supervisory signal. Testing - VA procedure used to determine the status of a system as intended by conducting periodic physical checks on water based fire protection systems such as waterflow tests, fire pump tests, alarm tests, and trip tests of dry pipe, deluge, or preaction valves. These tests follow up on the original acceptance test at intervals specified in the appropriate chapter of NFPA #25, 2002 edition. Upright Sprinkler - /A sprinkler designed to be installed in such a way that the water spray is directed upwards against the deflector. Water Spray Fixed System - V VA special fixed pipe system connected to a reliable fire protection water supply and equipped with water spray nozzles for specific water discharge and distribution over the surface or area to be protected. The piping system is connected to the water supply through an automatically or manually actuated valve that initiates the flow of water. An automatic valve is actuated by operation of automatic detection or manual release equipment installed in the same areas as the water spray nozzles. (In special cases, the automatic detection system may also be located in another area.) PREACTION SPRINKLER SYSTEMS - / designed for situations where there is danger of serious water damage. Water damage is usually caused by damaged sprinklers or broken piping. Under normal conditions there is no water in the piping. The air in the piping may or may not be is under pressure. A preaction valve prevents the water from entering the system. The valve is automatically opened when a fire detection system discovers that there is a fire or smoke condition. The preaction valve is tripped by 20