Calculation of Energy Losses and Discharge Coefficients for Venturi and Orifice Flowmeters, Study notes of Fluid Mechanics

This document details an experiment to quantify energy losses and estimate discharge coefficients for venturi and orifice flowmeters using data collected from an Edibon FME18 Flow Meter demonstration system. the calculation of pressure at critical points, energy loss, and the square root of pressure drop for each flow meter, as well as the use of equations and tables to determine the actual discharge coefficient.

Typology: Study notes

2021/2022

Uploaded on 08/01/2022

fioh_ji
fioh_ji ๐Ÿ‡ฐ๐Ÿ‡ผ

4.5

(70)

814 documents

1 / 10

Toggle sidebar

This page cannot be seen from the preview

Don't miss anything!

bg1
Bankston 1
Flowmeter Discharge Coefficient Estimation
Elizabeth Bankston Team 1
Abstract
An Edibon FME18 Flow Meter demonstration system was used to obtain experimental
values for this experiment. The data obtained was used to calculate energy loss, volumetric flow
rate, the square root of pressure drop, and estimate the discharge coefficient for a venturi
flowmeter, orifice flowmeter and a rotameter. The energy loss for a rotameter remained constant
at around 0.0023 kJ/kg, no matter what the flow rate was. The venturi had a similar theme at
around 0.0001 kJ/kg. The orifice meter lost more energy as the flow rate increased, with the
maximum energy lost being 0.001 kJ/kg. For a rotameter, flow rate had no effect on the square
root of pressure drop; while increasing flow rate increased the square root of pressure drop for
both the venturi meter and the orifice meter. The estimated discharge coefficient for the venturi
meter and orifice meter were, respectively, 0.656 and 0.680. For the venturi meter, the estimated
discharge coefficient was off by 0.324, which indicated that the systemโ€™s venturi meter was
operating at a lower efficiency than it should have. The large error could also be due to
technical errors or human errors. For the orifice meter, the estimated discharge coefficient was
off by 0.07, which indicated that the systemโ€™s orifice meter was operating more efficiently than
was expected.
Introduction
In any piping system, a fluid will travel through an array of pipe fittings, valves, and
elbows. When a fluid flows through such components, a pressure drop occurs due to the
frictional effects caused by changing the pathway of the fluid. Obstruction flowmeters are
devices used to measure fluid flow rate, by obstructing the flow and using a differential pressure
transducer to record the pressure before and after the obstruction (Cengel & Cimbala, 2014).
Orifice, venturi and nozzle flowmeters are all common types of obstruction flowmeters.
An orifice meter is one of the most common flow meters used (Wilhelm et al., 2004) and
one of the cheapest obstruction flowmeters (Cengel & Cimbala, 2014). The orifice meter is a
plate with a hole, significantly smaller than the inside pipe diameter, which is then placed inside
a pipe (Wilhelm et al., 2004). One of the negatives to using an orifice meter is that it causes a
sudden change in flow area, which leads to significant head loss or permanent pressure loss
(Cengel & Cimbala, 2014). Figure 1 shows the typical orifice flow pattern where P1-P2 indicates
significant head loss and P1-P3 indicates the permanent head loss.
pf3
pf4
pf5
pf8
pf9
pfa

Partial preview of the text

Download Calculation of Energy Losses and Discharge Coefficients for Venturi and Orifice Flowmeters and more Study notes Fluid Mechanics in PDF only on Docsity!

Flowmeter Discharge Coefficient Estimation

Elizabeth Bankston Team 1

Abstract

An Edibon FME18 Flow Meter demonstration system was used to obtain experimental

values for this experiment. The data obtained was used to calculate energy loss, volumetric flow

rate, the square root of pressure drop, and estimate the discharge coefficient for a venturi

flowmeter, orifice flowmeter and a rotameter. The energy loss for a rotameter remained constant

at around 0.0023 kJ/kg, no matter what the flow rate was. The venturi had a similar theme at

around 0.0001 kJ/kg. The orifice meter lost more energy as the flow rate increased, with the

maximum energy lost being 0.001 kJ/kg. For a rotameter, flow rate had no effect on the square

root of pressure drop; while increasing flow rate increased the square root of pressure drop for

both the venturi meter and the orifice meter. The estimated discharge coefficient for the venturi

meter and orifice meter were, respectively, 0.656 and 0.680. For the venturi meter, the estimated

discharge coefficient was off by 0.324, which indicated that the systemโ€™s venturi meter was

operating at a lower efficiency than it should have. The large error could also be due to

technical errors or human errors. For the orifice meter, the estimated discharge coefficient was

off by 0.07, which indicated that the systemโ€™s orifice meter was operating more efficiently than

was expected.

Introduction

In any piping system, a fluid will travel through an array of pipe fittings, valves, and

elbows. When a fluid flows through such components, a pressure drop occurs due to the

frictional effects caused by changing the pathway of the fluid. Obstruction flowmeters are

devices used to measure fluid flow rate, by obstructing the flow and using a differential pressure

transducer to record the pressure before and after the obstruction (Cengel & Cimbala, 2014).

Orifice, venturi and nozzle flowmeters are all common types of obstruction flowmeters.

An orifice meter is one of the most common flow meters used (Wilhelm et al., 2004) and

one of the cheapest obstruction flowmeters (Cengel & Cimbala, 2014). The orifice meter is a

plate with a hole, significantly smaller than the inside pipe diameter, which is then placed inside

a pipe (Wilhelm et al., 2004). One of the negatives to using an orifice meter is that it causes a

sudden change in flow area, which leads to significant head loss or permanent pressure loss

(Cengel & Cimbala, 2014). Figure 1 shows the typical orifice flow pattern where P 1

- P

2

indicates

significant head loss and P 1

- P

3

indicates the permanent head loss.

Figure 1: Pressure drop pattern caused by an orifice meter (Cengel & Cimbala, 2010).

A rotameter consists of a vertical tapered conical tube with a float inside that is free to

move. The float rises and falls as the fluid flows through the tapered tube, so that the float

weight, drag force, and buoyancy force balance each other and the net force acting on the float is

zero (Cengel & Cimbala, 2014). The flow rate is then determined by comparing the height of the

float to the scale on the side of the tube. Figure 2 shows how a rotameter balances out the forces

so that the net force equals zero and the scale to determine the flow rate. It is also of note that

rotameters have significantly more energy recovery than orifices, due to the more gradual

obstruction in a rotameter than in an orifice (Ramirez et al.). Although rotameters have more

energy recovery than orifices do, rotameters typically have an accuracy of + 5 percent; which

means that rotameters are not appropriate for applications that require precision measurements

(Cengel & Cimbala, 2014).

Figure 2: Typical operating system of a Rotameter (โ€œFlow: The Basics of Rotametersโ€,

The manometer heights were converted to meters before being used in equation (1),

which calculates pressure at the corresponding manometer location. After calculating the

pressure, energy loss was calculated for each flow meter in the system using equation (2); which

was derived from the energy equation when W turbine

and W pump

equal zero, V 1

and V 2

are equal,

and z 1

and z 2

are equal (equation (3)).

๐ฟ๐‘œ๐‘ ๐‘ 

โˆ†๐‘ƒ

๐œŒ

๐‘˜๐ฝ

๐‘˜๐‘”

๐‘ƒ 1

๐œŒ

๐‘‰ 1

2

2

1

๐‘๐‘ข๐‘š๐‘

๐‘ƒ 2

๐œŒ

๐‘‰ 2

2

2

๐‘ก๐‘ข๐‘Ÿ๐‘๐‘–๐‘›๐‘’

๐‘™๐‘œ๐‘ ๐‘ 

Where:

P = Pressure of the fluid at a certain point (Pa),

ฯ = density of water (kg/m

3

g = gravitational acceleration (m/s

2

h = manometer height (m)

E

Loss

= energy loss (kJ/kg),

โˆ†P = pressure drop and in this case permanent pressure loss (kPa),

ฮฑ = kinetic energy correction factor (unit less),

V = fluid velocity (m/s),

z = elevation (m),

W

turbine

= power required to run a turbine,

W

pump

= power required to run a pump.

It is important to take note of two things: 1) pressure should be converted to kilopascals

(kPa), so that conversion factor (i) can be used and result in kilojoules per kilogram (kJ/kg), and

  1. that the pressure drop (โˆ†P) is different for a venturi meter, an orifice meter and a rotameter.

Pressure drop for a venturi meter, an orifice meter, and a rotameter, when calculating energy

loss, can be found in table 1.

๐‘˜๐ฝ

๐‘˜๐‘”

3

(i)

Table 1: Pressure drops used for calculating energy loss.

Venturi Orifice Rotameter

โˆ†P P

1

โ€“ P

3

P

6

โ€“ P

8

P

4

โ€“ P

5

Energy losses for all three flowmeters was then plotted against the calculated flow rate.

Flow rate was calculated using equation (3) and the square root of pressure drop was calculated

using equation (4).

๐‘‰

๐‘ก

1 ๐‘š

3

1000 ๐ฟ

๐‘š

3

๐‘ 

๐‘š๐‘’๐‘ก๐‘’๐‘Ÿ

Where:

Q = volumetric flow rate (m

3

/s),

V = volume (L),

t = time (s),

Q

meter

= volumetric flow rate at the flow meter desired, also called square root of

pressure drop.

It is also important to note that the pressure drop for calculating the square root of

pressure drop is different than the pressure drop used to calculate energy loss for the venturi and

orifice meters (table 2).

meter showed similar energy losses; however, the orifice meter had the most energy loss as flow

rate increased (figure 3).

Figure 3: Energy losses (kJ/kg) versus flow rates for a Venturi, Rotameter, and Orifice flow

meter.

When calculating for energy loss, the pressure drops used were different than the pressure

drops used to calculate the flow rate at a specific flow meter. Calculating energy loss required

the permanent pressure loss; while calculating the flow rate at a specific flow meter required the

pressure drop across the flowmeter desired (figure 1). This is because just after the fluid moves

through the flowmeter, there is a large pressure drop, but as the fluid continues to travel through

the pipe some pressure is recovered. The difference between the inlet pressure and the pressure

downstream of the outlet is the permanent pressure loss; so when calculating energy loss, the

pressure recovered can be ignored, but the immediate pressure drop after an obstruction

determines the flow rate at that flowmeter.

When the calculated flow rate was plotted against the square root of pressure drop for the

rotameter, it was observed that the data created a vertical line (figure 4). This was suggests that

the pressure drop remains constant no matter what the flow rate is. Trend lines were created for

the venturi and orifice data to determine the slope of the line, which is used to calculate the

estimated discharge coefficient (figure 4). Equation (5) and table 2 were used to estimate the

y = 0.2925x

Rยฒ = 0.

y = 2.3135x

Rยฒ = 0.

0

0 0.00005 0.0001 0.00015 0.0002 0.00025 0.0003 0.00035 0.0004 0.

Energy losses (E) [kJ/kg]

Volumetic flow rate (Q) [m^3/s]

Venturi

Rotameter

Orifice

discharge coefficient for both the venturi meter and the orifice meter, which yielded 0.656 and

0.602 as the respective discharge coefficients (table 3).

Figure 4: Volumetric flow rate versus the square root of the pressure drop across either the

Venturi meter, the Orifice meter or the Rotameter.

Table 3: Data comparison of Theoretical and estimated Discharge Coefficients for Venturi

and Orifice Flowmeters.

Venturi Orifice

Discharge Coefficient (C d

) Discharge Coefficient (C d

Theoretical C d

0.95 9 Theoretical C d

Estimated C d

0.656 Estimated C d

In table 3 the theoretical discharge coefficient is shown for both the venturi and orifice

meters, which are calculated by using either equations (6), (7), and (8) or equations (9), (7), and

๐‘‘

  1. 1

8

  1. 71 โˆ—๐›ฝ

  2. 5

๐‘…๐‘’

  1. 75

y = 1E-05x

Rยฒ = 0.

y = 9E-06x

Rยฒ = 0.

0

0 10 20 30 40 50 60

Volumeteric flow rate (Q) [m^3/s]

Square root of pressure drop [Pa]

Venturi

Orifice

Rotameter

Conclusion

Using the data collected from a FME18 Flow Meter demonstration system, it was

possible to calculate the energy losses and discharge coefficients for a venturi meter and an

orifice meter. As flow rate increases, energy loss tends to increase as well, for the orifice and

venturi meters; whereas the rotameter tends to have a stable level of energy loss, no matter the

flow rate. The estimated discharge coefficient for a venturi meter was much lower than the

theoretical discharge coefficient; while the estimated discharge coefficient for an orifice meter

was higher than the theoretical discharge coefficient. The lower than expected estimated

discharge coefficient indicates that the venturi meter was operating at a lower efficiency than it

should have, while the orifice was operating at a higher efficiency than it should have.

References

Cengel, Y. A., & J. M. Cimbala. Fluid Mechanics: Fundamentals and Applications. McGraw-

Hill Companies Inc., 201 0. Web. 1 November, 2015.

Cengel, Y. A., & J. M. Cimbala. Fluid Mechanics: Fundamentals and Applications. New York:

the McGraw-Hill Companies Inc., 2014. Book. 1 November, 2015.

โ€œFlow: The Basics of Rotametersโ€ sensors ONLINE. 2002. Web. 1 November, 2015.

http://www.sensorsmag.com/sensors/flow/the-basics-rotameters- 1068

Ramirez, B. C., G. D. N. Maia, A. R. Green, D. W. Shike, L. F. Rodrรญguez, &R. S. Gates.

Technical note: DESIGN AND VALIDATION OF A PRECISION ORIFICE METER FOR

VENTILATION RATE CONTROL IN OPEN-CIRCUIT RESPIRATION CHAMBERS.

TRANSACTIONS OF THE ASABE. N.P. N.D. 57(6): 1865-1872. Web. 1 November

Wilhelm, L. R., D. A. Suter, & G. H. Brusewitz. Fluid flow. Chapter 4 in Food & Process

Engineering Technology. N.P. 2004: 65-110. St. Joseph Michigan: ASAE (Rev. Aug.

2005). Web. 1 November 2015.