▶ When paralleling two transformers, what should be checked to be sure of satisfactory results?. Answer: Polarity, impedance, and voltage ▶ A three phase transformer voltage is 66000/12470Y. Full load on high side is 13.1 amps. What are the amps on secondary? What is the KVA capacity?. Answer: 66000/12470=5. 5.29x13.1=69.29 or 69.3amps secondary 12470x69.3x1.
1000 =14. Or 15KVA capacity ▶ Why are relays used on OCB controls?. Answer: To sense overcurrent and trip OCB's ▶ High side fuses are ordinarily from 200 to 300% of full load current of transformers, if short circuit capacity will permit. What size fuse will be needed for a 66 KV, 1500KVA at 300%. Answer: 66000/1.732= 1500/3=500 KVA. or 500,000 KV 500,000/38106= 13. 13.1 x 300% = 39.3 or 40amp fuse ▶ Show how to calculate the proper tap to deliver 7620 volts from a
66000/12470Y transformer. Answer: 12470/1.732=7199.7 or 7200 420/7200=5% from 100=95% 66000 x .95 = 62700. Use a chart to change accordingly. ▶