JOURNEYMAN LINEMAN LATEST EXAM
PREP QUESTIONS AND ANSWERS PDF 2026
When paralleling two transformers, what should be checked to be sure of
satisfactory results?. Answer: Polarity, impedance, and voltage
A three phase transformer voltage is 66000/12470Y. Full load on high
side is 13.1 amps.
What are the amps on secondary?
What is the KVA capacity?. Answer: 66000/12470=5.29
5.29x13.1=69.29 or
69.3amps secondary
12470x69.3x1.732
-------------------
1000
=14.967
Or 15KVA capacity
Why are relays used on OCB controls?. Answer: To sense overcurrent
and trip OCB's
High side fuses are ordinarily from 200 to 300% of full load current of
transformers, if short circuit capacity will permit. What size fuse will be
needed for a 66 KV, 1500KVA at 300%. Answer: 66000/1.732=38106
1500/3=500 KVA. or
500,000 KV
500,000/38106= 13.1
13.1 x 300% = 39.3 or
40amp fuse
Show how to calculate the proper tap to deliver 7620 volts from a
pf2

Partial preview of the text

Download JOURNEYMAN LINEMAN LATEST EXAM PREP QUESTIONS AND ANSWERS PDF 2026 and more Exams Energy and Environment in PDF only on Docsity!

JOURNEYMAN LINEMAN LATEST EXAM

PREP QUESTIONS AND ANSWERS PDF 2026

▶ When paralleling two transformers, what should be checked to be sure of satisfactory results?. Answer: Polarity, impedance, and voltage ▶ A three phase transformer voltage is 66000/12470Y. Full load on high side is 13.1 amps. What are the amps on secondary? What is the KVA capacity?. Answer: 66000/12470=5. 5.29x13.1=69.29 or 69.3amps secondary 12470x69.3x1.

1000 =14. Or 15KVA capacity ▶ Why are relays used on OCB controls?. Answer: To sense overcurrent and trip OCB's ▶ High side fuses are ordinarily from 200 to 300% of full load current of transformers, if short circuit capacity will permit. What size fuse will be needed for a 66 KV, 1500KVA at 300%. Answer: 66000/1.732= 1500/3=500 KVA. or 500,000 KV 500,000/38106= 13. 13.1 x 300% = 39.3 or 40amp fuse ▶ Show how to calculate the proper tap to deliver 7620 volts from a

66000/12470Y transformer. Answer: 12470/1.732=7199.7 or 7200 420/7200=5% from 100=95% 66000 x .95 = 62700. Use a chart to change accordingly. ▶