UNIT 1B
CKT NO. DESCRIPTION LOAD (VA) DF (%) DEMAND (VA) AC VOLTS (V) CONNECTED LOAD CURRENT BREAKER CONDUCTOR CONDUIT SIZE (MM DIA.)
AMPS AT AF SIZE
1 LP - 1 260 100% 260 230 1.13 20 60 2 - 2.0mm² THHN WIRE 15
2 FAP - 1 80 100% 80 230 0.35 20 60 2 - 2.0mm² THHN WIRE 15
3 PP - 1 1000 50% 500 230 4.35 20 60 3 - 5.5mm² THHN WIRE 15
4 PP - 2 1000 50% 500 230 4.35 20 60 3 - 5.5mm² THHN WIRE 15
5 PP - 3 1080 50% 540 230 4.70 20 60 3 - 3.5mm² THHN WIRE 15
6 FCU - 1 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15
7 FCU - 2 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15
SPARE
8,020 6,480 34.87
UNIT 1C
CKT NO. DESCRIPTION LOAD (VA) DF (%) DEMAND (VA) AC VOLTS (V) CONNECTED LOAD CURRENT BREAKER CONDUCTOR CONDUIT SIZE (MM DIA.)
AMPS AT AF SIZE
1 LP - 1 280 100% 280 230 1.22 20 60 2 - 2.0mm² THHN WIRE 15
2 LP - 2 140 100% 140 230 0.61 20 60 2 - 2.0mm² THHN WIRE 15
3 FAP - 1 320 100% 320 230 1.39 20 60 2 - 2.0mm² THHN WIRE 15
4 PP - 1 1000 50% 500 230 4.35 30 60 3 - 5.5mm² THHN WIRE 15
5 PP - 2 1000 50% 500 230 4.35 30 60 3 - 5.5mm² THHN WIRE 15
6 PP - 3 1440 50% 720 230 6.26 30 60 3- 3.5mm² THHN WIRE 15
7 FCU - 1 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15
8 FCU - 2 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15
9 FCU - 3 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15
SPARE
11,080 9,360 48.17
UNIT 1D
CKT NO. DESCRIPTION LOAD (VA) DF (%) DEMAND (VA) AC VOLTS (V) CONNECTED LOAD CURRENT BREAKER CONDUCTOR CONDUIT SIZE (MM DIA.)
AMPS AT AF SIZE
1 LP - 1 240 100% 240 230 1.04 20 60 2 - 2.0mm² THHN WIRE 15
2 LP - 2 220 100% 220 230 0.96 20 60 2 - 2.0mm² THHN WIRE 15
3 FAP - 1 320 100% 320 230 1.39 20 60 2 - 2.0mm² THHN WIRE 15
4 PP - 1 1000 50% 500 230 4.35 30 60 3 - 5.5mm² THHN WIRE 15
5 PP - 2 1000 50% 500 230 4.35 30 60 3 - 5.5mm² THHN WIRE 15
6 PP - 3 1440 50% 720 230 6.26 30 60 3 - 3.5mm² THHN WIRE 15
7 FCU - 1 2300 100% 2300 230 10.00 30 60 3 - 3.5mm² THHN WIRE 15
8 FCU - 2 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15
9 FCU - 3 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15
10 FCU - 4 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15
13,420 11,700 58.35
UNIT 1E
CKT NO. DESCRIPTION LOAD (VA) DF (%) DEMAND (VA) AC VOLTS (V) CONNECTED LOAD CURRENT BREAKER CONDUCTOR CONDUIT SIZE (MM DIA.)
AMPS AT AF SIZE
1 LP - 1 300 100% 300 230 1.30 20 60 2 - 2.0mm² THHN WIRE 15
2 LP - 2 220 100% 220 230 0.96 20 60 2 - 2.0mm² THHN WIRE 15
3 FAP - 1 320 100% 320 230 1.39 20 60 2 - 2.0mm² THHN WIRE 15
4 PP - 1 1000 50% 500 230 4.35 30 60 3 - 5.5mm² THHN WIRE 15
5 PP - 2 1000 50% 500 230 4.35 30 60 3 - 5.5mm² THHN WIRE 15
6 PP - 3 1440 50% 720 230 6.26 30 60 3 - 3.5mm² THHN WIRE 15
7 FCU - 1 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15
8 FCU - 2 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15
9 FCU - 3 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15
10 FCU - 4 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15
13,480 11,760 58.61

Partial preview of the text

Download Load sched for checkpoint stf project and more Thesis Electrical Engineering in PDF only on Docsity!

UNIT 1B

CKT NO. DESCRIPTION LOAD (VA) DF (%) DEMAND (VA) AC VOLTS (V)

CONNECTED LOAD CURRENT BREAKER CONDUCTOR

AMPS AT AF SIZE CONDUIT SIZE (MM DIA.)

1 LP - 1 260 100% 260 230 1.13 20 60 2 - 2.0mm² THHN WIRE 15 2 FAP - 1 80 100% 80 230 0.35 20 60 2 - 2.0mm² THHN WIRE 15 3 PP - 1 1000 50% 500 230 4.35 20 60 3 - 5.5mm² THHN WIRE 15 4 PP - 2 1000 50% 500 230 4.35 20 60 3 - 5.5mm² THHN WIRE 15 5 PP - 3 1080 50% 540 230 4.70 20 60 3 - 3.5mm² THHN WIRE 15 6 FCU - 1 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15 7 FCU - 2 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15 SPARE 8,020 6,480 34.

UNIT 1C CKT NO. DESCRIPTION LOAD (VA) DF (%) DEMAND (VA) AC VOLTS (V)

CONNECTED LOAD CURRENT BREAKER CONDUCTOR

CONDUIT SIZE (MM DIA.)

AMPS AT AF SIZE

1 LP - 1 280 100% 280 230 1.22 20 60 2 - 2.0mm² THHN WIRE 15 2 LP - 2 140 100% 140 230 0.61 20 60 2 - 2.0mm² THHN WIRE 15 3 FAP - 1 320 100% 320 230 1.39 20 60 2 - 2.0mm² THHN WIRE 15 4 PP - 1 1000 50% 500 230 4.35 30 60 3 - 5.5mm² THHN WIRE 15 5 PP - 2 1000 50% 500 230 4.35 30 60 3 - 5.5mm² THHN WIRE 15 6 PP - 3 1440 50% 720 230 6.26 30 60 3- 3.5mm² THHN WIRE 15 7 FCU - 1 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15 8 FCU - 2 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15 9 FCU - 3 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15 SPARE 11,080 9,360 48.

UNIT 1D CKT NO. DESCRIPTION LOAD (VA) DF (%) DEMAND (VA) AC VOLTS (V)

CONNECTED LOAD CURRENT BREAKER CONDUCTOR

CONDUIT SIZE (MM DIA.)

AMPS AT AF SIZE

1 LP - 1 240 100% 240 230 1.04 20 60 2 - 2.0mm² THHN WIRE 15 2 LP - 2 220 100% 220 230 0.96 20 60 2 - 2.0mm² THHN WIRE 15 3 FAP - 1 320 100% 320 230 1.39 20 60 2 - 2.0mm² THHN WIRE 15 4 PP - 1 1000 50% 500 230 4.35 30 60 3 - 5.5mm² THHN WIRE 15 5 PP - 2 1000 50% 500 230 4.35 30 60 3 - 5.5mm² THHN WIRE 15 6 PP - 3 1440 50% 720 230 6.26 30 60 3 - 3.5mm² THHN WIRE 15 7 FCU - 1 2300 100% 2300 230 10.00 30 60 3 - 3.5mm² THHN WIRE 15 8 FCU - 2 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15 9 FCU - 3 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15 10 FCU - 4 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15 13,420 11,700 58.

UNIT 1E CKT NO. DESCRIPTION LOAD (VA) DF (%) DEMAND (VA) AC VOLTS (V)

CONNECTED LOAD CURRENT BREAKER CONDUCTOR

CONDUIT SIZE (MM DIA.)

AMPS AT AF SIZE

1 LP - 1 300 100% 300 230 1.30 20 60 2 - 2.0mm² THHN WIRE 15 2 LP - 2 220 100% 220 230 0.96 20 60 2 - 2.0mm² THHN WIRE 15 3 FAP - 1 320 100% 320 230 1.39 20 60 2 - 2.0mm² THHN WIRE 15 4 PP - 1 1000 50% 500 230 4.35 30 60 3 - 5.5mm² THHN WIRE 15 5 PP - 2 1000 50% 500 230 4.35 30 60 3 - 5.5mm² THHN WIRE 15 6 PP - 3 1440 50% 720 230 6.26 30 60 3 - 3.5mm² THHN WIRE 15 7 FCU - 1 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15 8 FCU - 2 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15 9 FCU - 3 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15 10 FCU - 4 2300 100% 2300 230 10.00 30 60 3 - 5.5mm² THHN WIRE 15 13,480 11,760 58.