INSTANT PDF DOWNLOAD — NERC prep test 1 with 200 questions and correct answers for 2025–2026 certification preparation. Covers grid reliability standards, system operations, emergency procedures, compliance rules, transmission operations, and exam-style practice questions designed to help candidates pass the NERC certification exam. NERC Exam, Power Systems, Grid Operations, Reliability Standards, Exam Prep, Practice Questions, Study Guide, Certification Test NERC Prep Test, NERC Exam PDF, 200 Questions NERC, NERC Practice Test, Grid Operations Exam, Power System Test, NERC Study Guide, Reliability Standards Exam, NERC Questions Answers, NERC Mock Exam, Transmission Operations Test, NERC Certification Prep, Power Grid Exam, NERC Test Prep, System Operations Questions, NERC Review Guide, Electrical Grid Exam, NERC Practice Questions, NERC Exam Prep, NERC Answer Sheet

Typology: Exams

2025/2026

Available from 05/19/2026

Prof.Stacey
Prof.Stacey 🇺🇸

5

(1)

323 documents

1 / 123

Toggle sidebar

This page cannot be seen from the preview

Don't miss anything!

bg1
1
/
123
NERC PREP TEST 1 01 I 200 QUESTIONS WITH CORRECT
ANSWERS
1.
1 .
If a
S00 kV transmission
line with
a
surge impedance loading
of 800 MW is
currently loaded at 1 400 MW, which of the following events would
most likely
occur?
a.
Generator MVAR output would
increase
b.
All
system capacitors would
trip off-line
c.
Generator MVAR output would
decrease
d.
All
automatic reactors would connect to the system>ANS a. Generator
MVAR output would
increase
2.
2. When
system conditions are such
that
emergency procedures are expect-
ed to be implemented,
which of the following actions should be considered
first?
a.
Shed firm load
b.
Implement
Active
Load
Management
c.
Return
outaged
equipment
to
service
d.
Request
a
voltage
reduction>ANS
c.
Return
outaged
equipment
to
service
3.
3. If your transmission path is
rated
for 1 200
MW and
1 000
MW are scheduled
on
it, but due to parallel flows the actual
flow is 1 300 MW, what action should
you
take?
pf3
pf4
pf5
pf8
pf9
pfa
pfd
pfe
pff
pf12
pf13
pf14
pf15
pf16
pf17
pf18
pf19
pf1a
pf1b
pf1c
pf1d
pf1e
pf1f
pf20
pf21
pf22
pf23
pf24
pf25
pf26
pf27
pf28
pf29
pf2a
pf2b
pf2c
pf2d
pf2e
pf2f
pf30
pf31
pf32
pf33
pf34
pf35
pf36
pf37
pf38
pf39
pf3a
pf3b
pf3c
pf3d
pf3e
pf3f
pf40
pf41
pf42
pf43
pf44
pf45
pf46
pf47
pf48
pf49
pf4a
pf4b
pf4c
pf4d
pf4e
pf4f
pf50
pf51
pf52
pf53
pf54
pf55
pf56
pf57
pf58
pf59
pf5a
pf5b
pf5c
pf5d
pf5e
pf5f
pf60
pf61
pf62
pf63
pf64

Partial preview of the text

Download NERC Prep Test 1 (200 Questions) PDF | 2026 Exam Questions & Answers and more Exams Power Electronics in PDF only on Docsity!

ANSWERS

    1. If a S00 kV transmission line with a surge impedance loading of 800 MW is currently loaded at 1 400 MW, which of the following events would most likely occur?

a. Generator MVAR output would increase

b. All system capacitors would trip off-line

c. Generator MVAR output would decrease

d. All automatic reactors would connect to the system>ANS a. Generator MVAR output would increase

    1. When system conditions are such that emergency procedures are expect- ed to be implemented, which of the following actions should be considered first?

a. Shed firm load

b. Implement Active Load Management

c. Return outaged equipment to service

d. Request a voltage reduction>ANS c. Return outaged equipment to service

    1. If your transmission path is rated for 1 200 MW and 1 000 MW are scheduled on it, but due to parallel flows the actual flow is 1 300 MW, what action should you take?

ANSWERS

a. Request that a phase shifting transformer be installed

b. Reduce interchange transactions impacting the path

ANSWERS

parameters

d. Reduce voltages on the transmission system>ANS c. Raise system voltages as high as possible, but within their operating parameters

    1. Which of the following actions should you take if an outage on a neigh- boring system has caused a violation on your system?

a. Open all tie-lines to your neighbor

b. Ask the Reliability Coordinator for assistance

c. Shed load to mitigate the violation

d. Wait for the neighboring system to contact you>ANS b. Ask the Reliability Coordi- nator for assistance

    1. If a SOL or IROL violation occurs due to transfers across the system and it is determined that parallel flows are contributing to the violation, what should the system operator do?

a. Place all system capacitors in service

b. Reduce system load

c. Inform the Reliability Coordinator

d. Dump firm load>ANS c. Inform the Reliability Coordinator

    1. While performing a pre-outage study, you identify that the transmission

ANSWERS

outage will cause a thermal violation on a parallel path, which of the following actions would be the first one you would implement?

ANSWERS

1 0. 1 0. If a Reliability Coordinator had to implement any type of line loading relief procedures, which of the following entities would they be coordinated with? Pick two.

a. Purchasing Selling Entities

b. Balancing Authorities

c. Transmission Operators

d. Load Serving Entities>ANS b. Balancing Authorities

c. Transmission Operators

1 1. 1 1. If a generator is lost in a neighboring Balancing Area, what would the impact be on the BAs transmission tie lines?

a. Nothing

b. A net increase of MW would come into your BAs system

c. A net increase of MW would go out of your BAs system

d. They would exceed their emergency limits>ANS c. A net increase of MW would go out of your BAs system 1 2. 1 2. According to the NERC Glossary, a constrained facility is defined as a transmission facility that is approaching, is at, or is beyond its?

ANSWERS

a. SOL or IROL

b. Normal voltage parameters

c. Available Transfer Capability

ANSWERS

1 5. 1 5. If your system is experiencing high system loads, high system imports, and transmission facilities loaded to 1 00%, which of the following situations would make the situation worse?

a. Loss of a distribution station

b. An internal generator tripping

c. A bulk capacitor connecting to the system

d. A 500 kV transmission line returned to service>ANS b. An internal generator tripping 1 6. 1 6. If a transmission line has a flow of 500 MW and the LODF for a parallel line due to the loss of this line is .25, how many MW will shift to this line if the line relays out of service?

a. 50 MW

b. 1 25 MW

c. 250 MW

d. 500 MW>ANS b. 1 25 MW

1 7. 1 7. If a transmission path is congested and it is determined that all curtail- able transactions have a 1 5% affect on the path, how many MW of transactions must be curtailed if 30 MW of relief is needed?

ANSWERS

a. 1 5 MW

b. 30 MW

ANSWERS

c. Within 24 hours

d. Within 30 days>ANS c. Within 24 hours

    1. According to NERC Standards, Transmission Operators and Balancing Authorities must provide their operating personnel with a minimum of how much training annually?

a. 2 days

b. 5 days

c. 1 0 days

d. 1 4 days>ANS b. 5 days

    1. If a major transmission facility were to relay out of service, who is the system operator to inform?

a. Only local management

b. All entities in the Interconnection

c. Any impacted system

d. NERC>ANS c. Any impacted system

    1. How is the reactive output of the generator increased?

ANSWERS

a. By raising the power factor

b. By adjusting the governor control manually

c. By adjusting the generator excitation

d. By changing the speed of the turbine>ANS c. By adjusting the generator

ANSWERS

a. Shunt reactors

b. Synchronous condenser

c. Generator

d. Capacitors>ANS a. Shunt reactors

    1. You report for work on a peak summer day with expected high temper- atures and load. What can you do to maintain an adequate system profile?

a. Switch reactors in service to remove the peak

b. Request all generators to reserve MVAR for the peak

c. Switch all capacitors in service without regard to voltage levels

d. Get under the voltage by placing capacitors in service while maintaining operating limits>ANS d. Get under the voltage by placing capacitors in service while maintaining operating limits

    1. What will be the reactive power output of a 200 MVAR shunt capacitor energized at 90% of its nominal voltage?

a. 1 20 MVAR

b. 1 50 MVAR

c. 1 62 MVAR

ANSWERS

d. 1 80 MVAR>ANS c. 1 62 MVAR

    1. When system conditions have caused the depletion of the system

reactive reserves, when should the reserves be restored?

ANSWERS

c. Current transformer

d. Potential transformer>ANS b. Static Var Compensators

    1. If it is desired to have a generator operate in the LEAD, what must the Generator Operator do to the generator?

a. Increase the excitation

b. Increase the hydrogen pressure

c. Decrease the excitation

d. Decrease the hydrogen temperature>ANS c. Decrease the excitation

    1. Which of the following reactive devices would be considered to be a dynamic reactive resource?

a. Transformer

b. Shunt reactor

c. Shunt capacitor

d. Generator>ANS d. Generator

    1. If the applied voltage of a capacitor experiences a 1 0% reduction from the rated voltage, what will be the impact on the capacitor output?

a. It will be increased by 1 0%

b. It will remain unchanged

ANSWERS

c. It will be reduced by 1 0%

d. It will be reduced by more than 1 0%>ANS d. It will be reduced by more than