A comprehensive overview of portable fire extinguishers, covering their classification, operation, and application. It delves into the different classes of fire extinguishers, their respective extinguishing agents, and the principles behind their effectiveness. The document also explores the importance of proper extinguisher selection and placement, emphasizing the need to consider hazard classification and occupancy type. It includes numerous questions and answers to reinforce understanding and promote critical thinking.
Typology: Exams
1 / 11
This page cannot be seen from the preview
Don't miss anything!







A Class A fire extinguisher with a numerical rating of 2 contains __ gallon of water ✔✔2.
A Class B foam extinguisher is not rated for which fuel ✔✔Cooking oil
A Class C agent must ✔✔not conduct electricity
A Class C extinguisher is rated for use on ✔✔energized electrical equipment
A Class K agent's effect on the fuel is known as ✔✔saponification
A fire extinguisher's agent is stored within its ✔✔cylinder
A loaded stream extinguisher is designed to ✔✔resist freezing
A portable fire extinguisher is bested suited for which situation ✔✔Fire in a wastebasket
A potential problem with application of a multipurpose dry chemical agent to a Class K fire is ✔✔neutralization of other agents applied to the fire
According of NFPA 10, the maximum floor area that can be protected by each extinguisher depends on the ✔✔occupancy type
All fire extinguishers are classified according to ✔✔the classes of fire on which they are effective
All portable fire extinguishers use which means for expelling their contents ✔✔pressure
Bromochlorodifluoromethane is a ___ agent ✔✔halogenated
Class D agents work primarily by ✔✔forming a crust over the fuel
Combustion begins when a fuel is heated to its ✔✔ignition point
For the purpose of fire extinguisher placement, what is the relationship between occupancy use category and hazard classification ✔✔They are not necessarily related
How do multipurpose dry chemical agents prevent rekindling of Class A fuel ✔✔By forming a crust over the fuel
If a private residence has a single fire extinguisher, where should it be located ✔✔Kitchen
In general , the maximum reach of CO2 extinguisher is __ feet ✔✔ 8
Requirements for placing and mounting portable fire extinguishers are sound in NFPA ✔✔ 10
The "P" in the acronym PASS, used in reference to fire extinguisher operation, stands for ✔✔pull
The hydrostatic test interval for a dry chemical extinguisher with a stainless steel shell is every __ years ✔✔ 5
The traditional symbol for a Class D fire extinguisher is a(n) ✔✔yellow star
The use of Halon 1211 is strictly controlled because it is ✔✔harmful to the environment
The weight of carbon dioxide is about __ the weight of air ✔✔one-and-a-half times
To qualify as a light hazard for the purpose of extinguisher election and placement, the majority of materials in the area must ✔✔be noncombustible
What does a rating of 40 on a Class B extinguisher mean ✔✔Sufficient extinguishing power for 40 square feet of burning fuel
What does it mean when a fire extinguisher has a pictograph with a red slash through it ✔✔Use on that class of fire could be hazardous
What expels the extinguishing agent from a pump tank water extinguisher ✔✔manual effort
What is the primary extinguishing mechanism of dry chemical agent ✔✔Interrupting the chemical chain reaction
What is the term for a water-soluble flammable liquid ✔✔Polar solvent
What is the term for the substance that puts out the fire ✔✔Extinguishing agent
What is used to pressurize a stored-pressure water extinguisher ✔✔Compressed air
What residue does a CO2 fire extinguisher leave when discharged;
A)Carbon
B)Iron oxide
C)Mineral salt
D)None ✔✔None
When approaching a fire with an extinguisher in hand, you should always have a(n) ✔✔exit route
Which agent is approved for use in a Class K system ✔✔Wet Chemical
Which agent is rated for use on Class A fires ✔✔Ammonium phosphate
Which class of fire extinguisher includes a number in its classification ✔✔A
Which class of fire includes cloth ✔✔A
Which class of fire includes flammable and combustible liquids ✔✔B
Which class of fire involves combustible cooking oils and fats ✔✔K
Which class of fire involves combustible metals ✔✔D
Which class of fire involves energized electrical equipment ✔✔C
Which feature of some carbon dioxide extinguisher makes them dangerous for use on class C fires ✔✔Metal horn
Which fire extinguishing agent is best for use on sensitive electronic equiment ✔✔Carbon dioxide
Which hazard category includes automotive service or repair facilities ✔✔extra
Which motion best accomplishes the removal of the pin and tamper seal from a portable fire extinguisher ✔✔twisting motion
Which of the following is commonly used as a dry chemical extinguishing agent ✔✔ammonium phosphate
Which of the following is one of the three basic components required for fire ✔✔oxygen
Which statement about dry chemical agents is correct ✔✔dry chemical agents are not subject to freezing
Which statement about foam fire extinguishers is correct ✔✔Class B foam extinguisher may be used to some effect on Class A fires
Which statement about the numerical rating of a Class K ✔✔There is no numerical rating for a Class K extinguisher
Which statement best summarizes when a dry chemical extinguisher should be serviced and recharged ✔✔After any discharge
Which statement is correct regarding Class D extinguishing agents ✔✔The specific agent must be matched to the specific fuel