






Study with the several resources on Docsity
Earn points by helping other students or get them with a premium plan
Prepare for your exams
Study with the several resources on Docsity
Earn points to download
Earn points by helping other students or get them with a premium plan
A detailed solution to homework assignment #4 for ece6323 power system protection at georgia institute of technology. It covers various aspects of power system protection, including fault analysis, relay settings, and distance protection. Detailed calculations and explanations for different fault scenarios, demonstrating the application of protection principles in real-world scenarios.
Typology: Assignments
1 / 11
This page cannot be seen from the preview
Don't miss anything!







ECE6323 Power System Protection - Spring 2024
Homework Assignment # 4 Solution
Problem P1 (10 points): Consider an 800 A circuit, 25.0 kV, 2 miles long, as it is illustrated in Figure
P1. The equivalent source impedance (on a 100 MVA basis) is:
z 1 =z 2 =j 0. 15 pu, z 0 =j 0. 18 pu
The CT is rated 1200:5A. The impedance of the circuit is:
z 1 =z 2 =j 0. 70 ohms/mile, z 0 =j 2. 10 ohms/mile
A time overcurrent relay is located at the indicated location. Assume that the relay is a numerical relay
that has instantaneous overcurrent protection as well as time-overcurrent protection with the following
selections:
Moderately Inverse: d (^ ) d
r
(^0 0). 02
Very Inverse: d (^ ) d
r
Extremely Inverse: d (^ ) d
r
have to be discrete values).
The relay settings are: pickup current=6A, time dial=1.0. Compute the time to trip for:
Solution:
6.25 ohms
base base base
z 1 = z 2 = j 0.7ohms/mile =j 0.112.. /p u mile
z 0 = j 2.1ohms/mile =j 0.336.. /p u mile
1
I j p u j j j j
I 2 =j1.9084.. p u
I (^) a = 0 p.u. ; I (^) b = −3.3054 p.u. ; Ic=3.3054 p.u.
Convert to Ampere:
100 / 3 3.3054 7.6335 kA 25
I b = − pu = −
Current in secondary of CT:
7.6335kA / 240 = 31.8 A
r 5. PickUp
The resulting time to trip is:
0
0
0
1.6324 s (Moderately Inverse)
1.2149 s (Very Inverse)
1.1627 s (Extremely Inverse)
t
t
t
1
I j p u j j j j
I 2 =j1.3369.. p u
I (^) a = 0 p.u. ; Ib = −2.3156 p.u. ; Ic=2.3156 p.u.
Convert to Ampere:
2.3156 5.3476 kA 25
I b = − pu = −j
Current in secondary of CT:
5.3476 / 240 kA = 22.2817 A
r 3. PickUp
The resulting time to trip is:
0
0
0
2.0510 s (Moderately Inverse)
2.0241 s (Very Inverse)
2.3264 s (Extremely Inverse)
t
t
t
0
0.6250 p.u. 0.15 0.15 0.18 0.224 0.224 0.
I j j j j j j j
I (^) F= 3 I 0 = −j1.8750 p.u.
Convert to Ampere:
1.8750 4.3301 kA 25
I (^) F= − pu = −
4.3301 kA / 240 = 18.0422 A
r 3. PickUp
The resulting time to trip is:
0
0
0
2.4272 s (Moderately Inverse)
2.9294 s (Very Inverse)
3.6282 s (Extremely Inverse)
t
t
t
Problem P2 (10 points) : Consider the 75 MVA, 230 kV /13.8 kV , z =j 0.118puthree-phase,
delta-wye connected variable tap step-up transformer indicated in Figure P2. This transformer is protected
with a differential relay. The delta side is the 13.8 kV side. The current transformer ratios arek and k 1 2
for the 230 kV and 13.8 kV sides, respectively.
Figure P 2
3 - phase balanced operating conditions. The operating current should be provided as a function of the current transformer ratio on the 13.8 kV side, the current transformer ratio on the 230 kV side, and the current of phase A on the 13.8 kV side of the transformer.
k = =
Then, calculate the operating current:
I op = − kA = A
First, calculate the transformation ratio:
k = =
Then, calculate the operating current:
I op = − kA = A
Question 2:
During a specific fault, the distance relay at one of the line ends recorded the following values:
Determine (a) the type of fault and (b) the location of the fault.
Solution:
Question 1:
j j j m e j
For numerical relays use:
j m e
Zone 1:
83.70 83. 1
j j z e e
Relay setting for zone 1: 5.38 Ohms, 83.7 degrees, compensation factor = 2. 53 𝑒−𝑗^11.^4
° , 3 cycle delay.
Zone 2:
83.70 83. 2
j j z e e
Relay setting for zone 2: 8.96 Ohms, 83.7 degrees, compensation factor = 2. 53 𝑒−𝑗^11.^4
° , 12 cycle delay.
Zone 3:
83.70 83. 3
j j z e e
Relay setting for zone 3: 17.92 Ohms, 83.7 degrees, compensation factor = 2. 53 𝑒−𝑗^11.^4
° , 30 cycle delay.
Question 2:
The type of fault is Line-to-Ground fault in Phase C.
Location of the fault:
Calculate the zero-sequence current from phase currents:
0 0.^
j I = e kA
Calculate the fault impedance:
0
c^ j f c
Z e I mI
Calculate the fault distance:
1
j f j
Z (^) e l miles e z
The fault distance is 42. 85 miles from the distance relay of the measurement (Zone 2).