Remove red we really were driving, Exercises of Philosophy of Love

Ggg that we are egg Trev RFD r3d

Typology: Exercises

2014/2015

Uploaded on 01/12/2023

Khattak1235
Khattak1235 🇵🇰

3 documents

1 / 42

Toggle sidebar

This page cannot be seen from the preview

Don't miss anything!

bg1
PDHonline Course E144 (4 PDH)
Power Factor in Electrical
Energy Management
Instructor: A. Bhatia, B.E.
2012
PDH Online | PDH Center
5272 Meadow Estates Drive
Fairfax, VA 22030-6658
Phone & Fax: 703-988-0088
www.PDHonline.org
www.PDHcenter.com
An Approved Continuing Education Provider
pf3
pf4
pf5
pf8
pf9
pfa
pfd
pfe
pff
pf12
pf13
pf14
pf15
pf16
pf17
pf18
pf19
pf1a
pf1b
pf1c
pf1d
pf1e
pf1f
pf20
pf21
pf22
pf23
pf24
pf25
pf26
pf27
pf28
pf29
pf2a

Partial preview of the text

Download Remove red we really were driving and more Exercises Philosophy of Love in PDF only on Docsity!

PDHonline Course E144 (4 PDH)

Power Factor in Electrical

Energy Management

Instructor: A. Bhatia, B.E.

PDH Online | PDH Center

5272 Meadow Estates Drive

Fairfax, VA 22030-

Phone & Fax: 703-988-

www.PDHonline.org

www.PDHcenter.com

An Approved Continuing Education Provider

Power Factor in Electrical Energy Management

Course Content

What is Power Factor?

Power factor is the percentage of electricity that is being used to do useful work. It is defined as the ratio of ‘active or actual power’ used in the circuit measured in watts or kilowatts (W or KW), to the ‘apparent power’ expressed in volt-amperes or kilo volt-amperes (VA or KVA).

The apparent power also referred to as total power delivered by utility company has two components.

  1. ‘Productive Power’ that powers the equipment and performs the useful work. It is measured in KW (kilowatts)
  2. ‘Reactive Power’ that generates magnetic fields to produce flux necessary for the operation of induction devices (AC motors, transformer, inductive furnaces, ovens etc.). It is measured in KVAR (kilovolt-Ampere-Reactance).

Reactive Power produces no productive work. An inductive motor with power applied and no load on its shaft should draw almost nil productive power, since no output work is being accomplished until a load is applied. The current associated with no-load motor readings is almost entirely "Reactive" Power. As a load is applied to the shaft of the motor, the "Reactive" Power requirement will change only a small amount. The ‘Productive Power’ is the power that is transferred from electrical energy to some other form of energy (i.e. such as heat energy or mechanical energy). The apparent power is always in always in excess of the productive power for inductive loads and is dependent on the type of machine in use. The working power (KW) and reactive power (KVAR) together make up apparent power, which is measured in kilovolt-amperes (KVA). Graphically it can be represented as:

Typical Un-improved Power Factor by Industry
Industry Power Factor

Auto Parts 75- Brewery 75- Cement 80- Chemical 65- Coal Mine 65- Clothing 35- Electroplating 65- Foundry 75- Forging 70- Hospital 75- Machine Manufacturing 60- Metalworking 65- Office Building 80- Oil field Pumping 40- Paint Manufacturing 65- Plastic 75- Stamping 60- Steel Works 65- Tool, dies, jigs industry 65-

Typical uncorrected industrial power factor is 0.8. This means that a 1MVA transformer can only supply 800KW or that a consumer can only draw 80 useful Amps from a 100Amp supply. To put it the other way, a 3-phase 100KW load would draw 172A per phase instead of the 139A expected. For inherently low power factor equipment, the utility company has to generate much more current than is theoretically required. This excess current flows through generators, cables, and transformers in the same manner as the useful current. If steps are

not taken to improve the power factor of the load, all the equipment from the power station to the installation sub-circuit wiring, has to be larger than necessary. This results in increased capital expenditure and higher transmission and distribution losses throughout the whole network.

To discourage these inefficiencies the electricity companies charge for this wasted power. These charges appear on electricity bills as "reactive power charges", "KVA maximum demand" or "KVA availability charges". For instance known information taken from billing about electrical system:

KVA = 1000, KW = 800, KVAR = 600, PF =.

Typical Utility Billing Structure Examples:

I) 90% Billing Structure - Where demand billed is based on 90% of the KVA or 100% of the KW - Whichever is greater. Because the facility has a power factor of 0.80 they will pay demand rates on 90% of the KVA 1000 x .90 = 900 KVA because it is the larger number (900 KVA > 800 KW). Thus the facility is paying a penalty on 100 KVA of unproductive power. Correcting the facility’s Power Factor to 90% + will eliminate this penalty cost.

II) 100% KVA + 100% KW Billing Structure - Where one rate is applied to 100% of the KVA and another rate is applied to 100% of the KW. Both are then added together to determine the total demand charged on the bill. If we correct the power factor to unity (KVA = KW or 800 KVA = 800 KW) we can recover costs paid on 200 KVA at *KVA rates. Assuming an equal rate is being paid for KVA and KW

Rather than pay demand costs on 1000 KVA + 800 KW = 1800 if the Power Factor = Unity we will pay demand costs on 800 KVA + 800 KW = 1600. Savings = 1800 -1600 = 200. (More examples are provided later in this paper).

*Note: Generally the cost per KVA is greater than the cost for KW. Thus the savings would be greater by correcting the power factor to unity.

The reactive power charges levied as penalties in the billing should always be regulated. The excess reactive currents and associated charges can be removed by a well-established technology called "Power factor correction". Simply put, this technology offsets the inductive reactive currents by introducing equal and opposite capacitive reactive currents. Typically this can reduce electricity bills by 5-8%, with a payback period of 12 to 18 months. In addition, the consumer shall gain from improved supply availability, improve voltage and reduced power losses.

1000 800 600 400 200 0 1 0.8 0.6 0.4 0.

POWER FACTOR

KW

Loss in distribution capacity

The figure below graphically displays the variation of the I 2 R losses in feeders and branches. Losses are expressed in percent as a function of power factor.

20

10 5

1 1 0.6 0. POWER FACTOR

LOSS(%)

Larger Investment

In case of expansion, a larger investment is required in the equipment needed to increase distribution capability of the installation, such as oversized transformers and switchgears.

Transformers

For an installation which requires 800KW, the transformer should be approximately:

800KVA for power factor = 100%

1000 KVA for power factor = 80%

1600 KVA for power factor = 50%

Large size conductors

The figure below shows a variation of a cross section of a conductor as a function of the power factor for a given useful power. This illustrates that when the power factor of an installation is low, the surcharge on the electricity bill is only part of the problem.

For instance, in an installation where no correction has been made and which has a power factor of 70%, the cross-section of the conductor must be twice as large as it would be if the power factor were 100%.

0.5 0.6 0.7 0.8^1

POWER FACTOR

0.3 0.4 0.

11.09 (^) 6.25 (^4) 2.79 (^) 2.04 (^) 1. 1.21 1

CONDUCTOR CROSS -SECTION

Practically speaking, when an installation uses its rated power capacity, the distribution cables within the installation are rapidly loaded to their full carrying capacity if the power factor decreases. Most often, as the need for energy in an installation expands, the first reaction is to double the distribution system although it would be less expensive to perform a correction of power factor on each load or group of loads.

Benefits of Power Factor Correction

Benefit 1 - Reduce Utility Power Bills In areas where a KVA demand clause or some other form of low power factor penalty is incorporated in the electric utility's power rate structure, removing system KVAR improves the power factor, reduce power bills by reducing the KVA. Most utility bills are influenced by KVAR usage.

Benefit 2 – Increase System Capacity

The power factor improvement releases system capacity and permits additional loads (motors, lighting, etc.) to be added without overloading the system. In a typical system with a 0.80 PF, only 800 KW of productive power is available out of 1000 KVA installed. By correcting the system to unity (1.0 PF), the KW = KVA. Now the corrected system will support 1000 KW, versus the 800 KW at the .80 PF uncorrected condition; an increase of 200 KW of productive power. This is achieved by adding capacitors which furnish the necessary magnetizing current for induction motors and transformers. Capacitors reduce the current drawn from the power supply; less current means lesser load on transformers and feeder

It is useful to have an idea of the value of the power factor of commonly used electrical equipment. This will give an idea as to the amount of reactive energy that the network will have to carry. Find below is the summary of power factor of commonly used electrical equipment.

Lighting

Incandescent Lamps: The power factor is equal to unity.

Fluorescent Lamps: Usually have a low power factor, for example, 50% power factor would not be unusual. They are sometimes supplied with a compensation device to correct low power factor.

Mercury Vapor Lamps: The power factor of the lamp is low; it can vary between 40% to 60%, but the lamps are often supplied with correction devices.

Distribution Transformer

The power factor varies considerably as a function of the load and the design of the transformer. A completely unloaded transformer would be very inductive and have a very low power factor.

Electrical Motors

Induction Motors: The power factor varies in accordance with the load. Unloaded or lightly loaded motors exhibit a low power factor. The variation can be 30% to 90%.

Synchronous Motors: Very good power factor when the excitation is properly adjusted. Synchronous motors can be over excited to exhibit a leading power factor and can be used to compensate a low power system.

Industrial Heating

With resistance, as in ovens or dryers, the power factor is often closed to 100%.

Welding

Electric arc welders generally have a low power factor, around 60%.

Other types of machinery or equipment those are likely to have a low power factor include:

Typical Un-improved Power Factor by Equipment
Equipment Power Factor

Air Compressor & Pumps (external Motors) (^) 75-

Hermetic Motors (compressors) 50- Arc Welding 35- Resistance Welding 40- Machining 40- Arc Furnaces 75- Induction Furnaces (60Hz) 100 Standard Stamping 60- High Speed Stamping 45- Spraying 60-

What causes low power factor?

From the above list, we can see that a low power factor can be a result of the design of the equipment, as in the case of welders, or it can be result from the operating conditions under which the equipment is used, as in lightly loaded induction motors which are probably the worst offenders.

Equipment Design

In an old installation, one is limited by the inefficiency of the existing system. However, given the opportunity to expand and purchase new equipment, one should consider some of the energy efficient electric motors that are available today.

Operating Conditions

Load: The power factor of an electrical motor reaches its maximum value under full load. The power factor decreases rapidly when the load decreases. The figure below symbolically illustrates the effect of the load on the power factor of a motor.

is used to measure the load current. The voltage is also measured. Now using the clamp on, power factor meter with appropriate CT, the power factor reading is noted.

The necessary data for desired power factor correction is current, line voltage and existing power factor. Now that the survey has been completed and it has been determined that power factor is a problem, the final step is to improve it. There are several approaches:

Power Factor Correction

Power factor correction can be made in two ways:

  1. Reduce the amount of reactive energy
  • Eliminate unloaded motors and transformers
  • Avoid supplying equipment with voltage in excess of the rated voltage
  1. Compensate artificially for the consumption of reactive energy with power factor capacitors. In practice, two type of equipment are available for power factor correction: a. Rotary Equipment: Phase advancers, synchronous motors and synchronous condensers. Where auto-synchronous motors are employed the power factor correction may be a secondary function. b. Capacitors: Power factor correction is achieved by the addition of capacitors in parallel with the connected motor circuits and can be applied at the starter, or applied at the switchboard or distribution panel. Capacitors connected at each starter and controlled by each starter is known as "Static Power Factor Correction" while capacitors connected at a distribution board and controlled independently from the individual starters is known as "Bulk Correction".

When installing equipment, the following points are normally considered:

  1. Reliability of the equipment to be installed
  2. Probable life of such equipment
  3. Capital cost
  4. Maintenance cost
  5. Running cost
  6. Space required and ease of installation

Generally the cost of rotating machinery, both synchronous and phase advancing, makes its use uneconomical, except where one is using rotating plant for a dual function – drive and

power factor correction. In addition the wear and tear inherent in all rotating machines involves additional expense for upkeep and maintenance.

Capacitors have none of these disadvantages. Compared with other forms of correction, the initial cost is very low, upkeep costs are minimal and they can be used with the same high efficiency on all sizes of installation. They are compact, reliable, highly efficient & convenient to install and lend themselves to individual, group or automatic method of correction. These facts indicate that generally speaking, power factor correction by means of capacitors is the most satisfactory and economical methods.

The static capacitor owing to its low losses, simplicity and high efficiency is now used almost universally for power factor correction.

What is a Capacitor?

Simply put, a capacitor is an electric device that can store electric charge for later release. Generally, capacitors are used in one of the three ways: to store and release energy, to discriminate between DC (direct current) and AC (alternating current) frequencies, and to discriminate between higher and lower AC frequencies.

A simple capacitor consists of two metal plates that are held parallel to each other with a small place between them. An insulating material called dielectric occupies the space. This insulating material can be made of many materials including oil, paper, glass, ceramics, and mica, plastic, or even air. Capacitance is a measure of the energy that a capacitor is capable of storing. The capacitance of a device is directly proportional to the surface areas of the plates and inversely proportional to the plates' separation.

How Capacitors Work

Induction motors, transformers and many other electrical loads require magnetizing current (KVAR) as well as actual power (KW). By representing these components of apparent power (KVA) as the sides of a right triangle, we can determine the apparent power from the right triangle rule: KVA^2 = KW 2 + KVAR^2. To reduce the KVA required for any given load, you must shorten the line that represents the KVAR. This is precisely what capacitors do.

KW

KVA Vk A

R }^

Supply this kilovars w ith

} Capacitors

Elim inate this KVA from KVA demandcharge

Correction Methods

Static or fixed Power Factor correction

Compensation on the load side of the AC motor starter (motor switched or "at the load"). Fixed capacitors provide a constant amount of reactive power to an electrical system. Primarily, fixed capacitors are applied to individual motor loads, but they can also be applied to the main power bus with proper treatment. Fixed capacitors are suitable for indoor or outdoor use. Fixed capacitors are available in low voltages (832 volt and below), from. KVAR up to 400 KVAR (If more than 400 KVAR is required, smaller units are paralleled together).

Central or Bulk Power Factor correction

Central power factor compensation is applied for electrical systems with fluctuating loads. The central power factor correction is usually installed at the main power distribution. The capacitors are controlled by a microprocessor-based relay, which continuously monitors the power factor of the total current supplied to the distribution board. The relay then connects or disconnects capacitors to supply capacitance as needed in a fashion to maintain a power factor better than a preset limit (typically 0.95). Ideally, the power factor should be as close to unity as possible.

When harmonic distortion is a concern, systems are built based on the principles explained under ‘Harmonic Distortion and Power Factor Correction’ later in this paper.

Determining Capacitor Requirements

The total KVAR rating of capacitors required to improve the power factor to any desired value can be calculated by using the tables published by leading power factor capacitor manufacturers.

Calculation Table for Capacitor Selection

To properly select the amount of KVAR required to correct the lagging power factor of a 3- phase motor you must follow the steps as stated. Step #1: Determine KW and Existing Power Factor. Step # 2: Existing Power Factor on Table, move across table to Desired Power Factor. The number represented is your multiplier number.

  • 1.0 0.99 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.90 0.85 0. Power factor Cos after improvement
  • 0.5 1.73 1.59 1.53 1.48 1.44 1.40 1.37 1.34 1.30 1.28 1.25 1.11 0.
  • 0.52 1.64 1.50 1.44 1.39 1.35 1.32 1.28 1.25 1.22 1.19 1.16 1.02 0.
  • 0.55 1.52 1.38 1.32 1.27 1.23 1.19 1.16 1.12 1.09 1.06 1.04 0.90 0.
  • 0.57 1.44 1.30 1.24 1.19 1.15 1.11 1.08 1.05 1.01 0.99 0.96 0.82 0.
  • 0.6 1.33 1.19 1.13 1.08 1.04 1.01 0.97 0.94 0.91 0.88 0.85 0.71 0.
  • 0.62 1027 1.23 1.06 1.01 0.97 0.94 0.90 0.87 0.84 0.81 0.78 0.65 0.
  • 0.65 1.17 1.03 0.97 0.92 0.88 0.84 0.81 0.77 0.74 0.71 0.69 0.55 0.
  • 0.67 1.11 0.97 0.91 0.86 0.82 0.78 0.75 0.71 0.68 0.65 0.62 0.49 0.
  • 0.7 1.02 0.88 0.81 0.77 0.73 0.69 0.66 0.62 0.59 0.56 0.54 0.40 0.
  • 0.72 0.96 0.82 0.75 0.71 0.67 0.63 0.60 0.57 0.53 0.51 0.48 0.34 0.
  • 0.75 0.88 0.74 0.67 0.63 0.58 0.55 0.52 0.49 0.45 0.43 0.40 0.26 0.
  • 0.77 0.83 0.69 0.62 0.58 0.54 0.50 0.47 0.43 0.40 0.37 0.35 0.21 0.
  • 0.8 0.75 0.61 0.54 0.50 0.46 0.42 0.39 0.35 0.32 0.29 0.27 0.
  • 0.82 0.70 0.56 0.49 0.45 0.41 0.37 0.34 0.30 0.27 0.24 0.21 0.
  • 0.85 0.62 0.48 0.42 0.37 0.33 0.29 0.26 0.22 0.19 0.16 0.
  • 0.87 0.57 0.42 0.36 0.32 0.28 0.24 0.20 0.17 0.14 0.11 0.
  • 0.90 0.48 0.34 0.28 0.23 0.19 0.16 0.12 0.09 0.06 0.
  • 0.91 0.45 0.31 0.25 0.21 0.16 0.13 0.09 0.06 0.
  • 0.92 0.43 0.28 0.22 0.18 0.13 0.10 0.06 0.
  • 0.93 0.40 0.25 0.19 0.15 0.10 0.07 0.
  • 0.94 0.36 0.22 0.16 0.11 0.07 0.
  • 0.95 0.33 0.18 0.12 0.08 0.
  • 0.96 0.29 0.15 0.09 0.
  • 0.97 0.25 0.11 0.
  • 0.98 0.20 0.
  • 0.99 0.

Example-

An energy audit for a facility indicates following measurements at the load side of the transformer; 480V, 1200A and 800 KW operating load.

i. What is the Power Factor? ii. How much Reactive Power (KVAR) is in the system?

Solution

i) To calculate the Power Factor, we must first calculate the KVA in the system.

Substitute the KVA into the Power Factor Formula

ii) To calculate the Reactive Power (KVAR) in the system requires re-arranging the formula

and solving for KVAR.

Example - 4

The measurement at the main distribution board of a manufacturing industry indicates 1000 KVA and 800 KW. Determine the system KVAR and PF of the facility. Determine also the KVAR required for achieving power factor of 0.95 while providing the same productive power of 800 KW?

Solution

Measured KVA = 1000

Measured KW = 800

i) System KVAR and PF of the facility

ii) System KVAR after power factor correction to.

System KVA after correction

System KVAR after correction

iii) Power capacitor KVAR rating

Power Capacitor KVAR = KVAR (uncorrected) – KVAR (corrected)

= 600 – 265 = 335 KVAR

We can use the multiplier table for capacitor selection (refer above) straight away when the KW load, uncorrected power factor and the desired power factor are known as shown in examples above.

Example - 5:

Billing based on KW Demand Charges An industrial plant has a demand of 1000 KW and operates at 80% power factor. The utility company supplying power to this unit requires minimum power factor of 85% and levies a KW demand charge of $8.00 in the electricity bill. Determine the savings possible by improving the power factor to a minimum required target of 0.85 along with the payback period of putting any investment on power factor correction.

Solution

i) The monthly KW billing is determined by the ratio of target power factor to the existing power factor times KW demand.

KW billing on power factor of 0.

The amount of monthly KW billing: 1000KW x 0.85 target PF / 0.80 existing PF = 1062 KW

Total demand charge @ $ 8.00 = 1062KW x $ 8.00 = $

ii) KVAR required to increase power factor from 0.8 to 0.

The multiplying factor = 0.13 (from the capacitor estimation table above)

Therefore KVAR required = 0.13 x 1000 = 130 KVAR

iii) Capacitor Investment