Transformer Waveforms: Observing Voltages and Currents in a Power Transformer, Lab Reports of Electrical and Electronics Engineering

An experiment to investigate the waveforms and interactions of various currents and fluxes in a power transformer. The configuration of the transformers used in the laboratory, the phasor diagram of voltages and currents, and the design of a system for observing the waveshapes. The experiment focuses on measuring the input current, core loss current, and magnetizing current, and analyzing their changes as the load is varied.

Typology: Lab Reports

Pre 2010

Uploaded on 02/13/2009

koofers-user-w2e
koofers-user-w2e 🇺🇸

9 documents

1 / 11

Toggle sidebar

This page cannot be seen from the preview

Don't miss anything!

bg1
Transformer Waveforms
EXPERIMENT Transformer Waveforms
Steady-State Testing and Performance of
Single-Phase Transformers
Waveforms
OBJECTIVE
The voltage regulation and efficiency of a distribution system are affected by the
electrical and magnetic characteristics of the transformers operating in the network. The
design of such a distribution system must consider these effects. This experiment
demonstrates the excitation current, magnetization current, AC saturation curve, and
core-loss current of transformers. These are investigated at various load conditions.
REFERENCES
1. “Electric Machinery”, Fourth Edition, Fitzgerald, Kinglsey, and Umans,
McGraw-Hill Book Company, 1983, Chapter 1.
2. “Electromagnetic and Electromechanical Machines”, Matsch, Leander W., Intext
Educational Publishers, 1972.
3. “Electromechanical Devices for Energy Conversion and Control Systems”, Del
Toro, Vincent, Prentice-Hall, Inc., 1968.
BACKGROUND INFORMATION
The basic theory of transformer operation is adequately explained in Reference 1.
For our purposes here we will concentrate on the test methods and the experimental set-
up of Figure 5.
Figure 1 shows the traditionally accepted electrical equivalent circuit for a power
transformer in steady-state. This particular equivalent circuit’s parameters are referred to
side 1. All relevant impedances, voltages, and currents are shown in the figure.
Revised: Spring 2005 1 of 11
pf3
pf4
pf5
pf8
pf9
pfa

Partial preview of the text

Download Transformer Waveforms: Observing Voltages and Currents in a Power Transformer and more Lab Reports Electrical and Electronics Engineering in PDF only on Docsity!

EXPERIMENT Transformer Waveforms Steady-State Testing and Performance of Single-Phase Transformers Waveforms

OBJECTIVE

The voltage regulation and efficiency of a distribution system are affected by the electrical and magnetic characteristics of the transformers operating in the network. The design of such a distribution system must consider these effects. This experiment demonstrates the excitation current, magnetization current, AC saturation curve, and core-loss current of transformers. These are investigated at various load conditions. REFERENCES

  1. “Electric Machinery”, Fourth Edition, Fitzgerald, Kinglsey, and Umans, McGraw-Hill Book Company, 1983, Chapter 1.
  2. “Electromagnetic and Electromechanical Machines”, Matsch, Leander W., Intext Educational Publishers, 1972.
  3. “Electromechanical Devices for Energy Conversion and Control Systems”, Del Toro, Vincent, Prentice-Hall, Inc., 1968.

BACKGROUND INFORMATION

The basic theory of transformer operation is adequately explained in Reference 1. For our purposes here we will concentrate on the test methods and the experimental set- up of Figure 5. Figure 1 shows the traditionally accepted electrical equivalent circuit for a power transformer in steady-state. This particular equivalent circuit’s parameters are referred to side 1. All relevant impedances, voltages, and currents are shown in the figure.

Figure 1: Steady-state equivalent circuit for power transformer.

It is important to note that for a typical power transformer the ratio of the parallel combination of the common leg impedances to the total impedance of either winding will exceed 200. Algebraically, this can be described as

R^ jX

R c Xm

(^11)

  • l

Figure 2: Winding configuration of laboratory transformers.

5, resistor R 1 is used to measure the current I 1. Similarly, resistor R 3 in Figure 5 is

used to measure current I 2. It is not so easy to measure the currents I c and I m , but we

can derive a voltage signal that is in phase with I c. The no-load voltage across

terminals Y 1 and Y 2 is

dt

d

V Y Y NY

=^ φ

1 − 2 (2.9)

which corresponds to E 2 ′ from Figures 1 and 4. Thus, we have a voltage signal that is

in phase with I c. The resistor R 2 in Figure 5 provides an adjustable signal that is in

phase with I c , yet the resistor is large enough to prevent excessive loading of the circuit.

The requirement for an adjustable signal becomes clear as the experiment is performed. We now have access to signals representing three currents. It is seen from Figure 1 that

I 1 =^ Ic + Im + I 2 ′

and, clearly

I m =^ I 1 − Ic − I 2 ′

Thus, we have signals for the three terms on the right side of Eq. 2.11, which means we should be able to measure the unknown by some differential means. Figure 4 shows a voltage source equivalent for the system of Figure 5 and clearly indicates a synthesis of Eq. 2.11. Therefore, the voltage signal that remains after the sources interact is

representative of I m.

Figure 4: Voltage source equivalent of Eq. 2.11.

NOTE: The voltage signals used above are adequate for waveshape analysis and phase relationships. They are not accurate for magnitude comparisons and should not be used for this purpose.

SUGGESTED PROCEDURE

The transformers used for this experiment are rated 120V-120V, 0.6kVA. There are three of them on each set of wall shelves. The set of windings connected to the source side of the transformer are called primary windings, and those connected to the load are named secondary windings. To achieve a 600 volt-ampere rating, these two sets of main primary and secondary windings must be in parallel. The other two windings are information (instrumentation) windings and are not designed to support a load.

Figure 1 defines the currents that are referred to throughout the experiment.

1. Figure 5 shows the connections that are used to view i 1 , i c , i m , and φ m. The

first transformer is identical to the transformer being tested and is used to help prevent ground loops between the source and the instrumentation.

NOTE: The signal being observed as is a voltage from the 6V winding, but is

a signal that has the same waveform as i

i c

c.^ Also, the φ m signal is an integrated

voltage signal having the waveform of φ m.

2. Add a secondary resistive load by connecting the circuit of Figure 6 to the transformer load connection of Figure 5 and set input voltage to 120 V AC

maintain constant. Adjust R 3 to remove the load current i 2 from the oscilloscope

display. R 2 may also need to be readjusted slightly. Record the AC saturation

curve as the load current is varied between 0, 1.0, 1.5, 2.0 and 2.5 AMPS. Describe in the report the change in the peak-to-peak magnitude of flux as the load resistance is changed. For different primary voltages, describe the changes in the waveforms and curves

of i 1 , i c , i m , φ m and saturation as the load is varied. From this information,

comment on the transformer’s performance at different voltages.

3. Bypass the integrator by reconnecting the oscilloscope leads directly to terminals

and Y. Turn the calibration knob of the corresponding differential

amplifier fully counter-clockwise. This will prevent the amplifier from running over the maximum allowed range. Observe the relative magnitudes and phase angles of the terminal voltage and as the load resistance is varied. Magnitudes can be obtained directly from the meters on the panel. To obtain phase angle between signals displayed, use the MEASURE capability of the scope with selections of PERIOD and DELAY from the vertical menu. Determine the period of the voltage waveform because this signal is harmonic free.

Y 3 4

i 1

Without Cap Load current Voltage VT Current I 1 Phase VT to I (^1)

acitor

I 2 0.0A 1.0A 2.0A

r input. The lab presently does not contain the try an RL load type. ith Capa Load current Voltage VT Current I 1 Phase VT to I (^1)

Connect the large capacitor found on the shelf in parallel with the load resistor. Again observe the relative magnitudes and phase angles at the transforme proper inductor to W citor

I 2 0.0A 1.0A 2.0A

  • Figure
  • Figure