JANUARY 2022 41
structural ANALYSIS
Engineering projects and building code provisions can often seem
like Rorschach tests where two people looking at the same thing
can draw sharply different conclusions. This article reviews the two-
stage analysis procedure in ASCE 7-16, Minimum Design Loads for
Buildings and Other Structures, to consider if the provisions are an
innocent inkblot or possibly may be interpreted differently by some.
Engineers simplify what is too complex to solve and what is too
complex to solve efficiently in practice. The simplification imposes
the obligation to validate that it does not result in a solution that
works for the simplified model but is invalid for the complex realities.
Because simplification is often an imperfect step away from reality,
simplification incurs the obligation of conservatism. The authors’
purpose is to explain how the two-stage analysis simplification can be
applied inappropriately to allow for designs that do not provide the
level of safety intended by the code. This article also offers remedies
to prevent future misuse of this procedure.
A bold and useful simplification in the code’s seismic provisions
is the equivalent lateral force (ELF) procedure, predicated on the
assumption of approximately equal deformation distribution in one
dimension over the structure’s height. But an efficient and ubiquitous
building type like podium construction with several stories of light
framing perched on one or more levels of concrete (or concrete with
concrete masonry) framing is not consistent with the assumptions
inherent in the ELF procedure. Using ELF for podium construction
can result in mass from the heavier base being applied as inertial
loads to the flexible upper portion. Rather than subject podium
construction to the rigors and expense of a dynamic analysis, code
authors opted for another simplification to keep the ELF procedure
on the table for the design of podium construction by adopting the
two-stage analysis provisions first introduced in the 1988 Uniform
Building Code (UBC).
Conceptually, the two-stage analysis introduces a reasonable sim-
plification to reflect the physical phenomenon of a rigid base not
amplifying ground motions to more flexible stories perched above.
Further, it appropriately builds in conservatism because analyzing
a single building as two separate shorter buildings results in shorter
periods for individual building portions, and therefore, equal or
greater base shear coefficients for each portion of the structure.
However, as demonstrated by the example building described later,
this conservatism can be insufficient compensation if the two-stage
analysis technique masks the deleterious effects of a base with a
torsional irregularity. The two-stage analysis allows the flexible
upper portion to be designed as a separate structure fixed at its
base using the ELF or modal response spectrum procedure. The
reactions from the upper portion are transferred to the rigid base
(lower portion), amplified, not reduced, as appropriate for relative
seismic response modification factor (R) and redundancy factor
(ρ) values. Consistent with the procedure’s imposition of a static
force at the top of the rigid base, the lower portion is designed
using the ELF procedure.
Code Provisions
The two-stage analysis procedure provisions from ASCE 7-16, Section
12.2.3.2 are listed below:
a. The stiffness of the lower portion must be at least 10 times the
stiffness of the upper portion.
b. The period of the entire structure shall not be greater than 1.1
times the period of the upper portion considered as a separate
structure fixed at the base.
c. The flexible upper portion shall be designed as a separate
structure using the appropriate values of R and ρ.
d. The rigid lower portion shall be designed as a separate struc-
ture using the appropriate values of R and ρ. The reactions
from the upper portion shall be those determined from the
analysis of the upper portion amplified by the ratio of the R/ρ
of the upper portion over R/ρ of the lower portion. This ratio
shall not be less than 1.0.
e. The upper portion is analyzed with the equivalent lateral force
or modal response spectrum procedure, and the lower portion
is analyzed with the equivalent lateral force procedure.
To the main point, these provisions strain the obligation to validate
the simplification. Only (a) and (b) provide restrictions to apply the
procedure; the other items specify how the procedure is used. While
item (a) imposes a relative stiffness requirement, the stiffness param-
eter is undefined. More importantly, the stiffness obligation does not
mandate that the lower portion have properties that provide support
equivalent to ā€œfixed at the base.ā€ While item (b) imposes a require-
ment to compare dynamic properties of the two portions, the period
comparison does not ensure the lower portion responds rigidly as the
procedure allows the engineer to assume. In the authors’ opinion,
although compliance with item (b) is not uniformly adhered to, the
provision at least helps diligent practitioners and code enforcement
officials keep designs closer to the code intent of a fixed base.
Figure 1. Example building's finite element model.
continued on next page
Two-Stage Analysis Loophole
By Steven Shepherd, S.E., and James McDonald, S.E.
pf3
pf4

Partial preview of the text

Download Two-Stage Analysis Loophole and more Study notes Structural Analysis in PDF only on Docsity!

structural ANALYSIS

E

ngineering projects and building code provisions can often seem like Rorschach tests where two people looking at the same thing can draw sharply different conclusions. This article reviews the two- stage analysis procedure in ASCE 7-16, Minimum Design Loads for Buildings and Other Structures , to consider if the provisions are an innocent inkblot or possibly may be interpreted differently by some. Engineers simplify what is too complex to solve and what is too complex to solve efficiently in practice. The simplification imposes the obligation to validate that it does not result in a solution that works for the simplified model but is invalid for the complex realities. Because simplification is often an imperfect step away from reality, simplification incurs the obligation of conservatism. The authors’ purpose is to explain how the two-stage analysis simplification can be applied inappropriately to allow for designs that do not provide the level of safety intended by the code. This article also offers remedies to prevent future misuse of this procedure. A bold and useful simplification in the code’s seismic provisions is the equivalent lateral force (ELF) procedure, predicated on the assumption of approximately equal deformation distribution in one dimension over the structure’s height. But an efficient and ubiquitous building type like podium construction with several stories of light framing perched on one or more levels of concrete (or concrete with concrete masonry) framing is not consistent with the assumptions inherent in the ELF procedure. Using ELF for podium construction can result in mass from the heavier base being applied as inertial loads to the flexible upper portion. Rather than subject podium construction to the rigors and expense of a dynamic analysis, code authors opted for another simplification to keep the ELF procedure on the table for the design of podium construction by adopting the two-stage analysis provisions first introduced in the 1988 Uniform Building Code (UBC). Conceptually, the two-stage analysis introduces a reasonable sim- plification to reflect the physical phenomenon of a rigid base not amplifying ground motions to more flexible stories perched above. Further, it appropriately builds in conservatism because analyzing a single building as two separate shorter buildings results in shorter periods for individual building portions, and therefore, equal or greater base shear coefficients for each portion of the structure. However, as demonstrated by the example building described later, this conservatism can be insufficient compensation if the two-stage analysis technique masks the deleterious effects of a base with a torsional irregularity. The two-stage analysis allows the flexible upper portion to be designed as a separate structure fixed at its base using the ELF or modal response spectrum procedure. The reactions from the upper portion are transferred to the rigid base (lower portion), amplified, not reduced, as appropriate for relative seismic response modification factor (R) and redundancy factor (ρ) values. Consistent with the procedure’s imposition of a static force at the top of the rigid base, the lower portion is designed using the ELF procedure.

Code Provisions

The two-stage analysis procedure provisions from ASCE 7-16, Section 12.2.3.2 are listed below: a. The stiffness of the lower portion must be at least 10 times the stiffness of the upper portion. b. The period of the entire structure shall not be greater than 1. times the period of the upper portion considered as a separate structure fixed at the base. c. The flexible upper portion shall be designed as a separate structure using the appropriate values of R and ρ. d. The rigid lower portion shall be designed as a separate struc- ture using the appropriate values of R and ρ. The reactions from the upper portion shall be those determined from the analysis of the upper portion amplified by the ratio of the R/ρ of the upper portion over R/ρ of the lower portion. This ratio shall not be less than 1.0. e. The upper portion is analyzed with the equivalent lateral force or modal response spectrum procedure, and the lower portion is analyzed with the equivalent lateral force procedure. To the main point, these provisions strain the obligation to validate the simplification. Only (a) and (b) provide restrictions to apply the procedure; the other items specify how the procedure is used. While item (a) imposes a relative stiffness requirement, the stiffness param- eter is undefined. More importantly, the stiffness obligation does not mandate that the lower portion have properties that provide support equivalent to ā€œfixed at the base.ā€ While item (b) imposes a require- ment to compare dynamic properties of the two portions, the period comparison does not ensure the lower portion responds rigidly as the procedure allows the engineer to assume. In the authors’ opinion, although compliance with item (b) is not uniformly adhered to, the provision at least helps diligent practitioners and code enforcement officials keep designs closer to the code intent of a fixed base.

Figure 1. Example building's finite element model.

continued on next page

Two-Stage Analysis Loophole

By Steven Shepherd, S.E., and James McDonald, S.E.

42 STRUCTURE magazine

Changes to the two-stage analysis procedure proposed for ASCE 7-22 clarify the application of the ASCE 7-16 provisions but do not result in significant changes to the procedure or the criteria to qualify for its use. While it is necessary to stipulate quantification of the relative stiff- ness and period, leaving these as the only criteria to qualify for the simplifying procedure expands eligibility beyond the original intent to simplify the design of podium construction. In this case, the engi- neering quest to quantify the dynamic nature of the podium obscures the requirement rather than clarifying it. The loosely defined relative stiffness requirement between the upper and lower portions and the absence of a requirement specifying the lower portion to provide a fixed base to the upper portion throw open the gates for misapplication of the two-stage provisions. The following sections demonstrate some examples of potential misapplications. Although this article elucidates a flaw in the provisions, a call to action requires the specter of significant consequences – remedied with the analysis of an example building.

Height Limit Loophole

One of the proposed updates for ASCE 7-22 clarifies that the height limits for a given seismic design category (SDC) and building type can be applied as measured from the base of the upper portion. So, if a special reinforced concrete shear wall is being designed in SDC D and is limited to 160 feet per Table 12.2-1, the designer can design a 181-foot-tall building using the two-stage analysis if the bottom 21 feet are at least 10 times as stiff as the upper 160 feet. Based on parametric studies, this is most likely to be the case for a building of similar con- struction and where the upper portion is more than seven times the height of the lower portion. At that aspect ratio for such a building, the bending flexibility contributes enough to the response to meet the required stiffness ratio. The period of the 181-foot-tall structure would be within the 1.1 limit of item (b) using the approximate period equation of ASCE 7. Note that buildings this tall can usually qualify for both requirements (a) and (b) by virtue of their height, even if the base of the structure is not significantly different than the upper stories.

Torsional Irregularity Loophole

The two-stage analysis provisions do not address the effect that a torsional irregularity in the stiffer lower portion can have on the flexible upper portion. Torsional irregularities are common in podium construction where entry-level architectural features or sloping sites can necessitate an eccen- tric layout of seismic shear-resisting elements. A torsional response in the base of the structure results in a rotational accelera- tion being input into the upper portion. Moreover, if the center of rigidity at the base is eccentric to the center of mass in both horizontal directions, the response in the two horizontal directions will be coupled for both the lower and upper portions. Neither of these effects is cap- tured in a two-stage analysis, where the upper portion is analyzed as a separate structure. Furthermore, ASCE 7-

applies limitations, penalties, and other requirements to structures with torsional and extreme torsional irregularities, but the two-stage analysis allows the upper portion of a building to potentially avoid these requirements even if it is significantly affected by an extreme torsional irregularity in the base. The code requirements associated with a torsional irregularity include the following:

  • A 25% increase in demands for collectors, collector connections, and connections of diaphragms to vertical elements of the seis- mic force-resisting system for buildings in SDC D through F
  • The structure must be analyzed using a 3-D model
  • The effects of accidental torsion must be amplified per Section 12.8.4.
  • Structures in SDC D through F exceeding 2 stories must be analyzed using a dynamic analysis
  • In addition to the above requirements, an extreme torsional irregularity also requires a 30% increase in the horizontal seis- mic forces through a redundancy factor, ρ, of 1.3 for buildings in SDC D through F

Example Building

The authors developed a 3-D finite element model of a 13-story concrete shear wall building with a large podium level having an extreme torsional irregularity at the bottom story ( Figure 1, page 41 ) to investigate the effects that a torsionally irregular base can have on the upper portion of a building. The example building is set in a location of high seismicity, such as near a significant fault in coastal California classified as SDC D with seismic parameters SDS and SD of 1.57g and 0.65g, respectively. The building has rigid concrete diaphragms (assumed) and four full- height core shear walls at the center of the tower plan area. Relative to the tower, the bottom story has twice the area, a larger unit weight, and two additional perimeter shear walls at two orthogonal building edges. These conditions are typical of a tower and base configuration, plaza construction, and construction on a sloping site. To compare the seismic demands obtained from a single, coupled building analysis to those obtained using the two-stage analysis pro- cedure, the authors also created separate models of the 12-story upper portion and one-story base, as shown in Figures 2 and 3 , respectively. The building qualifies for the two-stage analysis procedure with a base approximately 160 times stiffer than the upper portion and a combined model period 1.1 times that of the upper portion. With accidental torsion effects included, the largest ratio of maximum story drift to average story drift at any level in the upper portion building model is 1.39, giving that model a torsional irregularity per ASCE 7-16, Table 12.3-1, but not an extreme tor- sional irregularity. On the other hand, the bottom level of the full structure has an extreme torsional irregularity. Because of the torsional irregularities, both the separate upper portion model and the coupled full building model are required to be analyzed using a dynamic analysis per ASCE 7-16, Table 12.6-1, and accidental torsion effects need to be included for both models. Both build- ings were analyzed using a Response Figure 2. Example building's upper portion. Spectrum Analysis (RSA) with forces

References

ASCE, 2016, Minimum Design Loads and Associated Criteria for Buildings and Other Structures , ASCE 7-16, American Society of Civil Engineers, Reston, VA.

ASCE, 2021, Proposed Changes to Minimum Design Loads and Associated Criteria for Buildings and Other Structures , ASCE 7-22, American Society of Civil Engineers, Reston, VA.

International Conference of Building Officials, 1988, Uniform Building Code , Whittier, CA.