Chapter 4 fault analysis, Lecture notes of Electrical Engineering

Notes of Fault Analysis

Typology: Lecture notes

2015/2016

Uploaded on 03/04/2016

Azmira.Ibrahim
Azmira.Ibrahim 🇲🇾

4

(1)

1 document

1 / 25

Toggle sidebar

This page cannot be seen from the preview

Don't miss anything!

bg1
DEK3213 Electric Power System
Fault Analysis
85
Chapter 4
Fault Analysis
4.1. Introduction
Fault is the unintentional connecting together of two or more conductors which
ordinary operates with a difference of potential between them. Connection
between conductors may be physical metallic contact or through an arc.
There are two categorized of fault in power system:
(i) Three phase balanced fault
Three phase fault
Three phase to earth fault
(ii) Three phase unbalanced fault
Line to line fault
Line to earth fault
Double line to earth fault / line to line to earth fault
When fault occurred in a system, it will produced large current to flow through
the transmission line and will caused damage to the equipment located at the end
of the network.
Actually these faults can be isolated using relays and circuit breakers which are
used to separate the network from the high current.
Nowadays, FACTS (Flexible AC Transmission System) and Custom Power are
use to solve the fault problem.
In fault analysis, values of these currents are calculated for the differences types
of faults at various locations in the system.
The data/ result obtained are then serve to determine the settings of relays which
control the circuit breakers
2.2. Types of Fault
a) one line to earth fault
pf3
pf4
pf5
pf8
pf9
pfa
pfd
pfe
pff
pf12
pf13
pf14
pf15
pf16
pf17
pf18
pf19

Partial preview of the text

Download Chapter 4 fault analysis and more Lecture notes Electrical Engineering in PDF only on Docsity!

Chapter 4

Fault Analysis

4.1. Introduction  Fault is the unintentional connecting together of two or more conductors which ordinary operatesbetween conductors may be physical metallic contact or through an arc. with a difference of potential between them. Connection  There are two categorized of fault in power system: (i) Three phase balanced fault  Three phase fault  Three phase to earth fault (ii) Three phase unbalanced fault  Line to line fault  Line to earth fault  Double line to earth fault / line to line to earth fault  When fault occurred in a system, it will produced large current to flow through the transmission line and will caused damage to the equipment located at the end of the network.  Actually these faults can be isolated using relays and circuit breakers which are used to separate the network from the high current.  Nowadays, FACTS (Flexible AC Transmission System) and Custom Power are use to solve the fault problem.  In fault analysis, values of these currents are calculated for the differences types of faults at various locations in the system.  The data/ result obtained are then serve to determine the settings of relays whichcontrol the circuit breakers

2.2. Types of Fault

a) one line to earth fault

b) line to line fault

c) double line to earth fault

d) three phase to earth fault

e) three phase fault

Objectives of fault analysis. i) ii) To determine maximum and minimum 3-phase short circuit current.To determine the unsymmetrical fault current for single or double line to earth, line to line fault and other faults. iii) To determine fault current distribution & busbar voltage levels during faults. iv) Investigating of the operation of protection relays.

X x pu

X x pu

X x pu

G

G

G

' 3

' 2

' 1

Step 1

G

F

0.24pu 0.27pu 1

2

G1 G

1

2 0.1pu 1

2

N

Step 2 : Short circuit voltage source

N

1

2 0.1pu 0.27pu 1

2 0.24pu 1

2

F

Step 3 : Reduction of impedance network.

F N

0.054pu 1

2

Step 4 : Put back voltage sources and short circuit FN, than findIF

V (^) pu  1. 0 pu  0 o

F N

0.054pu 1

2 G

I I xI x MVAkV A

I pu Fact Fpu Base

o Fpu

  1. (^5360) ( 118 ) 5431

, ,

,   

Load MVA / Fault MVA

MVA

MVA

X

MVA

OR

MVA

kV

xV xI

eq

Base

B F

Example 2 An interconnected generator-reactor system is shown in Figure. The base values for the given percent reactances are the ratings of the individual pieces of equipment. A 3θ short circuit occurs at point F. determine the fault current and the fault kVA if the busbar line o line voltage is 11kV. Choose 50MVA as base values.

I x kVMVA A

MVA M MVA kVA f

f

  1. (^2521110666)

050. 246 203.^252203252

Example 3:

Find the fault current in the following. Take base of 10MVA, 6.6kV.

6.6/33kV,x=6%, 5000kVA

T

R 20ohm

6.6/33kV,x=5%, 7500kVA

G

6.6kV,x=10%,6000kVA

G1 T

6.6,x=12%,4000kVA

Solution:

X x pu

X x pu

X x pu

X x pu

T

T

G

G

2

1

2

1

Z pu

X x MVAk pu

Z X X X X X

T

r

T G T G T r

2

1 1 2 2

z

B pu F

base Base base

I

I I

x k

M

xkV

I MVA

 3 ^10333  174. 95

I (^) FIpuxIbaseXVpupuxIB  0. 3341 pupux 174. 95  523. 82 A

Fault MVA 3 I (^) F VB  3 x 523. 82 x 33 k  30 MVA

Example 4 In the network shown in figure 1, each line has a reactance of 0.4Ω/km. using a base of 100MVA, calculate the 3θ symmetrical fault current in amperes and the corresponding fault level (in MVA) at busbars A and B.

100MVA,x=0.15pu

9 km

75MVA ,x=0.14pu

T2 10 km

100MVA ,x=0.17pu

66kV

40MVA ,x=0.12pu

60MVA,x=0.15pu

A

33kV

C

G2 D 10 km

G1 T

(^9) km^ B

66kV

T

12 km

Figure 1 Solution:

Line CA 12km(0.4Ω/km) = 4.8Ω Line CD 9km(0.4Ω/km) = 3.6Ω Line DA 10km(0.4Ω/km) = 4.0Ω Choose 100MVA as base value. Then:

L

1 2

1 2

L

1^ L3 2

1 2

j0.17 j0.

1 2

j0.

1 2

j0.

1 2

j0.083^1 j0.

j0.

j0.

j0.

j0.

1 2

j0.

j21.

j0. 1 2

L

L

L

j0.

1 2 j0. j0.083^1

1 2

1 2

C 1 2

1 2 F

j0. B

j0. 1 2

j0.32 N

A

1 2

1 2 1 2

1puV V N

1 2 F

Example 5 Refer to figure below; Generator G 1 (^) , G 2  25 MVA , x  0. 1 pu Motor M  20 MVA , x  0. 1 pu Transmission lines AB, BC,CD,AC,BD. Impedance 10Ω each. Take base of 100MVA, 33kV. Assume machines produces rated voltage of 33kV at no load. By network reduction , find fault current and fault MVA level at busbar D, if the fault at busbar C what will be the fault MVA at busbar C. G

M

D

G

B C

A

Solution Base 100MVA , 33kV (a) Fault occur at busbar D

0.1pu

10ohm

D

C 10 ohm

A

M

10ohm 10 ohm

0.1pu

10 ohm

B

(b) Fault occur at busbar C

I I xI X x xMVAk x A kA

X

F pu B T

T (^11003330). 773751 1749. 55 22. 61

Fault MVA  3 V (^) B IF  3 x 33 kx 22. 61 k  129. 24 MVA

4.4. UNBALANCE FAULT USING SYMMETRICAL COMPONENTS Three unbalanced phasors of a three-phase system can be resolved into three balancedsystems of phasors:-

a) Positive-sequence components - consisting of three phasors equal in magnitude, displaced from each other by 120º in phase, and having the same phase sequence as the original phasors.(Subscript 1 show the positive sequence) b) Negative-sequence components - consisting of three phasors equal in magnitude, displaced from each other by 120º in phase, and having the phase sequence opposite to that of the original phasors. .(Subscript 2 show the negative sequence) c) Zero-sequence components – consisting of three phasors equal in magnitude and with zero phase displacement from each other. .(Subscript 0 show the zero sequence)

In matrix form, the voltages are:-

2

1

0 2

2 1

a

a

a c

b

a V

V

V

a a

a a V

V

V

So,

Vb 1

Va 1

Vb Va 1

Vb Vc

Va 2 Vbo

Vc 1

Vco Vao

c

b

a a

a

a V

V

V

a a

a a V

V

V

2

2 2

1

0 1

In matrix form, the currents are:-



2

1

0 2

2 1

a

a

a c

b

a I

I

I

a a

a a I

I

I

So,

c

b

a a

a

a I

I

I

a a

a a I

I

I

2

2 2

1

0 1

The unloaded symmetrical voltage component can be written as:

2

1

0 2

1

0 2

1

0 0 0

a

a

a a a

a

a I

I

I

Z

Z

Z

E

V

V

V

a)Line to earth fault

Ec c Ib

Eb

Fault occur at line a. 0

Io = Ia

Ia

Ea

0

a

Zn

Ic

b

b c

a I I

V

(^1120)

1 1 1 2 1 0

1 1 1 2 1 0 0

Z Z Z

I E

I Z I Z I Z E

V

V E I Z I Z I Z

a^ a

a a a a

a

a a a a a

Ia

Z2^ -

Vao Zg

Z

Va

Z

Zg

+^ Ea

3Zn Iao

3Zn

Ia

Ia

Ea

Z

Va

b) Line to line fault

Eb

Zn

Ic

Io = In

c

Ib

Ia

b

a

0

Ea

Ec

b c

a

b c I I

I

V V

c

b

a a

a

a V

V

V

a a

a a V

V

V

2

2 2

1

0 1

b

b

a a

a

a V

V

V

a a

a a V

V

V

2

2 2

1

0 1

Va (^) 1  Va (^2) IIba ^ ^0 Ic

c

c a

a

a I

I

a a

a a I

I

I 0

2

2 2

1

0

2 1

a a

a I I

I

 because 3

2

1 a^ c

a c I^ I

I I

1

1 2

1

0 1

1

a

a a a

a

a I

I

Z

Z

Z

E

V

V

V

Va 0  0 because Ia 0  0

(^112)

1 2 1 1

1 1 2

1 1 1

Z Z I E

I Z E I Z

V I Z

V E I Z

a^ a

a a a

a a

a a a

 

 

 

  2

1

(^10)

2

1 1 0 0 0 1

Z

Z

Z

Z

Z

Z

Z

2

1

0 1

1

1

1 1

1 1

1 1

2

1

0 0

2

1

0 a

a

a a Z

Z

Z a a

a a

a a I

I

I

E

E I Z

E I Z

E I Z

Z

Z

Z

So,

21 1 2

11 1 1 1

01 1 0

a a a

a a a a

a a a

E ZI Z I

E ZI Z ZE I

E ZI Z I

Knowing that IaIa 1  Ia 2  Ia 0  0 ,



 

  ^  

   

      

      

2

1 0 1 1 0 2

0 2

2

1 1 1

1 1 0

1 1 0 2

2

1 1 1 1 2

1 1 0 1

1 1 0

2

1 1 1 1

1 1 0

1 1

( ) 1

0

0

Z

Z Z I Z Z Z

E Z Z

Z

I Z Z

I Z Z

I Z Z

E Z

E

Z

I Z Z

E Z

E Z

I Z Z

E Z

I Z Z

E

Z

E I Z Z

E Z

E I Z Z

E I Z

a a

a a a a a

a a a a a a a

a a a a a a a

0 2

(^1102)

0 2

(^110202)

0 2 1 2 1 0

0 2 2

1 0 2 0 0 2 1 0 2

1 0 2

1 2

1 0 0 2 1

0 2

Z Z

Z Z Z

I E

Z Z

Z Z Z Z Z

I E

Z Z Z Z ZZ

E Z Z

Z

ZZ Z

Z

Z Z ZZ Z

I E Z Z

I

Z

Z

Z

Z Z Z

E Z Z

a^ a

a a

a a a

a a

Tutorial 4 FAULT ANALYSIS

  1. Refer to the figures 1, 2 ,3 ,4 and 5 below, draw an impedance diagram. Calculate the fault MVA if fault occur at : (a) Lets take 60MVA as new base.

G

118kV

60MVA0.1pu 20MVA0.09pu G

20MVA0.08pu G

Figure 1 (b). Choose 50MVA as base values.