Kashaf Abdullah 2019-EE-060, B
POWER SYSTEM OPERATION AND CONTROL
LABORATORY MANUAL 3
Economic Dispatch of Generators in the Power System (Lossless System)
Course Learning Outcome (CLO):
CLO1: ‘Adapt engineering methods in optimal power flow’.
Task 3-a
Perform Economic Dispatch calculations for the generators of the following power system.
Cost Curves of the Generators
Department of Electrical Engineering UET Lahore
pf3
pf4
pf5
pf8
pf9
pfa
pfd
pfe
pff
pf12

Partial preview of the text

Download System in normal state and more Lab Reports Power Distribution and Utilization in PDF only on Docsity!

Kashaf Abdullah 2019 - EE- 060 , B

POWER SYSTEM OPERATION AND CONTROL

LABORATORY MANUAL 3

Economic Dispatch of Generators in the Power System (Lossless System) Course Learning Outcome (CLO): CLO1: ‘Adapt engineering methods in optimal power flow’. Task 3-a

Perform Economic Dispatch calculations for the generators of the following power system.

Cost Curves of the Generators

Transmission Line Data

Line R X B

L1- 3 0 0.24 0.

L3- 4 0 0.03 0.

L1- 2 0 0.06 0.

L2- 5 0 0.12 0.

L2- 4 0 0.18 0.

L2- 3 0 0.18 0.

L4- 5 0 0.24 0.

Calculations

Perform manual calculations to find the power generated by each of the generators in the power

system shown above in order to meet the load in the most economical way.

Registration No: 2019 - EE- 060

(Note: In case, if 𝑦 = 0 and 𝑧 = 0, then assume 𝑦 = 5 and 𝑧 = 2) Assume: 𝝀 = 𝒚 + 𝒛 𝝀=

Task 3A P1(MW) P2(MW) P3(MW) Calculated 140.625 180.55 69. Simulated 141 181 70

Assignment

Perform the calculations for the following three load settings (What are the incremental costs

in each case). Display the incremental cost value in PWS. Attach your simulation results.

a) 1160MW

b) 654MW

c) 300MW

Part (A)

Calculations :

PartA(1160) P1(MW) P2(MW) P3(MW)

Calculated 400 460 300

Simulated 400 460 300

Part (B)

Calculations :

PartB(654) P1(MW) P2(MW) P3(MW) Calculated 235.44 264.833 153. Simulated 235 265 154

Part (C)

Calculations :

Simulation PartC(300):

Part_C P1(MW) P2(MW) P3(MW) Calculated 100 150 50 Simulated 100 150 50