A practice exam or q&a related to backflow prevention in plumbing systems. It covers various topics such as cross-connections, backflow prevention devices, testing procedures, and code requirements. Detailed explanations and answers to multiple-choice questions, making it a valuable resource for individuals preparing for exams or seeking to deepen their understanding of backflow prevention principles. The comprehensive nature of the content, with over 30 pages of questions and answers, suggests that this document could be useful for university-level courses or training programs related to plumbing, water systems, or environmental engineering.
Typology: Exams
1 / 32
This page cannot be seen from the preview
Don't miss anything!

























A cross-connection may be a permanent piping arrangement or a(n) ____? A. Backflow preventer B. Church symbol C. OSHA hazardous area designation D. Railroad and highway intersection sign E. Temporary hose bibb connection - Answer: Temporary hose bibb connection The isolation of a plumbing water system hazard requires____? A. Appliance protection B. Building quarantine C. High-hazard protection D. Meter protection E. Toxin monitoring - Answer: Appliance protection
A direct cross-connection suggests the piping system may be subjected to ____? A. Backpressure or backsiphonage B. Backsiphonage only C. Periodic inspection D. Sustained pressure E. Toxic materials - Answer: Backpressure or backsiphonage A pipe restriction's flow velocity increase may allow ____? A. Aspiration B. Backpressure C. Low turbulence D. Pressure head E. Pressure surges - Answer: Aspiration Water supply contamination from backflow may result in ____? A. A bad taste B. Coloration C. Death D. Odor or smell E. Pipe wall mineral deposit flaking - Answer: Death To prevent backflow, an atmospheric vacuum breaker is primarily designed to ____? A. Allow air into the outlet piping system
D. 12 in. (30 cm) E. 18 in. (46 cm) - Answer: 1 in. (2.5 cm) A hose-bibb connection is required to have a permanently installed ____? A. Atmospheric vacuum breaker B. Backflow preventer C. Pressure vacuum breaker D. Shut-off valve E. Spill-resistant vacuum breaker - Answer: Atmospheric vacuum breaker Atmospheric vacuum breakers must not be subject to continuous water pressure for more than ___ hr. A. 3 B. 6 C. 12 D. 18 E. 24 - Answer: 12 A submerged atmospheric vacuum breaker may be considered a(n) _____? A. Backflow preventer B. Cross-connection C. Expensive elbow D. Typical installation E. Useful training photo - Answer:. Cross-connection
Flow from the outlet of an atmospheric vacuum breaker must not reach a _____? A. Closed tank B. Section of straight tubing C. Submerged inlet D. Toxic substance E. Valve - Answer: Valve An atmospheric vacuum breaker is not required to have a(n) _____? A. Annual field test B. Installation elevation C. Installation inspection D. Label E. Usage limitaion - Answer: Annual field test The air-inlet valve of an atmospheric vacuum breaker is help closed by____? A. Atmospheric pressure B. Cotter pins C. Gravity D. Spring tension E. Water pressure - Answer: Water pressure Pressure vacuum breaker shut-off valves and test cocks will avoid freeze damage if winterized by ____? A. Leaving all valves fully open B. Rotating ball valve handles to 45 degree angle
D. Elevated piping E. Irrigation sprinkler heads - Answer: Irrigation sprinkler heads The minimum loading to open a pressure vacuum breaker's air-inlet valve is ____? A. 1 psi (6.89 kPa) B. 2 psi (13.8 kPa) C. 3 psi (20.7 kPa) D. 4 psi (27.6 kPa) E. 5psi (34.5 kPa) - Answer: 1 psi (6.89 kPa) The recorded value of a pressure vacuum breaker check valve is determined when ____? A. Both shut-off valves are closed B. The high-bleed valve is opened C. The air-inlet valve opens D. Water stops flowing from test cock 1 E. Water stops flowing from test cock 2 - Answer: Water stops flowing from test cock 2 Pressure vacuum breaker shut-off valves must be _____ valves. A. Angle B. Gate C. Globe D. Regulating E. Tightly closed - Answer: Tightly closed
An indication that a pressure vacuum breaker is undersized for its application is _____? A. Air-inlet valve leakage B. Bonnet distortion C. Chatter or noise during flow D. Disc pitting E. Spring elongation - Answer: Chatter or noise during flow Continuous flow from a pressure vacuum breaker's test cock 2 with shut-off valve 2 open and shut-off valve 1 closed is an indication of _____? A. Backpressure backflow B. Backsiphonage backflow C. A failed air-inlet valve D. A leaking check valve E. A leaking or damaged shut-off valve 1 - Answer: Backpressure backflow Pressure vacuum breakers may be used on the following applications except ____? A. High hazard/backsiphonage B. High hazard/continuous pressure C. Low hazard/backpressure D. Low hazard/backsiphonage E. Low hazard/intermittent pressure - Answer: Low hazard/backpressure
B. 2 gpm (7.6 l/min) C. 3 gpm (11.4 l/min) D. 4 gpm (15.1 l/min) E. 5 gpm (18.9 l/min) - Answer: 2 gpm (7.6 l/min) A field test report for a double check valve assembly will include the manufacturer's name, model, size, and _____? A. Body material B. Date of manufacture C. Serial number D. Working pressure (maximum) E. Working temperature (maximum) - Answer: Serial number Double check valve assembly components must be _____? A. Bronze B. Independently acting C. Plastic D. Rubber E. Spring activated - Answer: Independently acting After the repair of a double check valve assembly, a field test is required for the _____? A. Check valve number 1 B. Component repaired C. Entire assembly
D. Tester's personal records only E. Shut-off valve tightness - Answer: Entire assembly Prior to testing the check valves in the direction of flow on a double check valve assembly using a high and low side on the gauge, a tester must first ____? A. Determine the tightness of shut-off valve number 2 B. Notify the owner of the water shut-off C. Record the water supply line pressure D. Submit the test report to the water supply E. Test check valve number 2 with backpressure - Answer: Determine the tightness of shut-off valve number 2 A double check valve assembly installed in a vertical flow down orientation is only allowed ______? A. In a basement or vault B. If the assembly was tested and approved as such C. If the check weight does not compress the spring D. On fire-suppression systems E. On water supply service connections - Answer: If the assembly was tested and approved as such A check valve field test reported value of 0.8 psid (5.5 kPa) suggests _____? A. A passing check valve B. A broken or failed spring C. Debris in the check seat
E. Water hammer or hydraulic shock - Answer: Water hammer or hydraulic shock Backpressure to a reduced pressure principle assembly fouled check valve number 2 will likely _____? A. Dissipate through the air-vent B. Force the relief valve to open and discharge C. Have no visible effect D. Push the check valve closed E. Remain in the system - Answer: Force the relief valve to open and discharge An air-gap separation must be maintained at a reduced pressure principle assembly's _____? A. Build drain B. Domestic Supply C. Indirect drain outlet D. Relief valve discharge E. Stationary sensor - Answer: Relief valve discharge A reduced pressure principle assembly's buffer can be described as a ____? A. Soft-seated check upstream of the assembly B. Difference between the values for check valve 1 and check valve 2 C. Difference between the check valve 1 loading and the relief valve opening point D. Difference between the relief valve opening point and check valve 2 E. Sum of the check valve 1 loading and the relief valve divided by 2 - Answer: Difference between the check valve 1 loading and the relief valve opening point
When a reduced pressure principle assembly is installed vertically, the relief valve discharge must be _____? A. To a floor drain 2 times the piping size B. Higher than check valve number 1 C. Lower than check valve number 1 D. Lower than check valve number 2 E. Piped with the flow directed down - Answer: Lower than check valve number 1 The maximum protection provided by a reduced pressure principle assembly is ____? A. High hazard/backpressure B. High hazard/backsiphonage C. High hazard/backpressure or backsiphonage D. Low hazard/backpressure E. Low hazard/backpressure or backsiphonage - Answer: High hazard/backpressure or backsiphonage The reduced pressure principle assembly's number 2 check valve is loaded to close the valve with a minimum differential pressure of _____? A. 1 psid (6.9 kPa) B. 2 psid (13.9 kPa) C. 3 psid (20.7 kPa) D. 4 psid (27.6 kPa) E. 5 psid (34.5 kPa) - Answer: 1 psid (6.9 kPa)
E. 5 - Answer: 1 An air-gap separation's hazard classification is _____? A. High hazard/backsiphonage B. High hazard/backpressure C. Low hazard/backsiphonage D. Low hazard/backpressure E. High or low hazard/backsiphonage only - Answer: High or low hazard/backsiphonage only With the exception of a drinking fountain, the minimum air-gap separation is _____? A. 0.5 in. (1.3 cm) B. 1.0 in. (2.5 cm) C. 1.5 in. (3.8 cm) D. 2.0 in. (5.1 cm) E. 3.0 in. (7.6 cm) - Answer: 1.0 in. (2.5 cm) Water discharged through an air gap to an open tank surface has a pressure of ____? A. 0 psi absolute
B. 0 psi atmospheric C. 0 psi gauge D. Static line pressure E. Vapor pressure - Answer: 0 psi atmospheric Air-gap separations must be ____? A. Classified B. Inspected annually C. Laboratory listed D. Tested and repaired E. Tested with a sight tube - Answer: Inspected annually When close to two intersecting walls, an air-gap separation is increased from 2 diameters to _____ diameters. A. 2. B. 3 C. 3. D. 4 E. 4.5 - Answer: 4 An air-gap separation is mandatory between the potable supply and a(n) _____? A. Bakery dough mixer B. Isolation assembly C. Pressure washer D. Sanitary sewer
B. Fixture outlet C. Gate valve D. Service connection E. Water meter - Answer: Fixture outlet A spool is used to connect a ____? A. Copper and ductile iron pipe B. Copper and PVC pipe C. Disc retainer and valve guide D. Potable and non-potable system E. Test cock - Answer: Potable and non-potable system A fire sprinkler system's backflow protection for a black-iron pipe system is typically ____? A. An air-gap separation B. A double check valve assembly C. A reduced pressure principle assembly D. A reduced pressure detector assembly E. No protection required - Answer: A double check valve assembly The dual check with an intermediate vent is used primarily for ____? A. Commercial boilers B. Industrial process water piping C. Hose bibbs D. Low-pressure residential boilers
E. Swimming pool chlorinators - Answer: Low-pressure residential boilers A hose connection vacuum breaker's maintenance includes _____? A. Check disc replacement B. Diaphragm replacement C. Draining for winterization D. Replacement every 2 years E. Water flushing - Answer: Draining for winterization Pressure loss per foot of elevation rise is ____? A. 0.43 psi (2.99 kPa) B. 0.50 psi (3.45 kPa) C. 1.0 psi (6.89 kPa) D. 2.0 psi (13.9 kPa) E. 2.3 psi (15.9 kPa) - Answer: 0.43 psi (2.99 kPa) When the water velocity increases, the ____? A. Atomospheric pressure decreases B. Gauge pressure decreases C. Gauge pressure increases D. Head loss does not change E. Water temperature lowers - Answer: Gauge pressure decreases An indirect cross-connection suggests the system may be subject to ____? A. An air gap separation