BACKFLOW PREVENTION PRACTICE TEST
While conducting the first test on a Spill Resistant Vacuum Breaker, when the vent
screw is removed the air inlet valve opens and the gauge falls to zero. What would this
indicate? - Answers - A faulty check valve
The differential pressure relief valve of a reduced pressure principle assembly is closed
by: - Answers - System water pressure
While conducting the first test on a double check assembly. When the number the
number three test cock is opened, water continues to flow and will not stop. What is the
proper way to proceed? - Answers - Observe the reading on the gauge
A booster pump is utilized to increase water pressure for the water user. When water
pressure is increased within the internal water system to a higher pressure than the
water suppliers pressure this creates: - Answers - Back pressure
When testing a double check valve assembly, the test gauge and water in a sight tube
must: - Answers - Remain at the same level
The first recordable value a tester must obtain when testing a reduced pressure
principle backflow prevention assembly is: - Answers - The relief valve opening point
When conducting a test on a reduced pressure principle assembly, when flushing the kit
in preparation for the test, the tester should close things in what order? - Answers -
Close the #2 SOV, high side bleed and then the low side bleed
Degree of hazard determines what? - Answers - What type of backflow assembly to
install
While conducting a test on a double check valve assembly, when the tester opens the
test cock with the sight tube, the gauge stays at the upper end of the scale. What would
this indicate? - Answers - The gauge and the sight tube have been incorrectly applied
A tester has conducted a test on a reduced pressure principle assembly with the
following results - relief valve opened at 3.2, #2 check held tight against backpressure
and the #1 check held steady differential of 4.9. What does this indicate? - Answers -
The assembly has failed the test
The largest size of backflow prevention assemblies are: - Answers - 2" for pressure
vacuum breakers, spill resistant vacuum breakers and 12" for double check valves and
reduced pressure principle assemblies
pf3

Partial preview of the text

Download BACKFLOW PREVENTION PRACTICE TEST and more Exams Social Sciences in PDF only on Docsity!

BACKFLOW PREVENTION PRACTICE TEST

While conducting the first test on a Spill Resistant Vacuum Breaker, when the vent screw is removed the air inlet valve opens and the gauge falls to zero. What would this indicate? - Answers - A faulty check valve The differential pressure relief valve of a reduced pressure principle assembly is closed by: - Answers - System water pressure While conducting the first test on a double check assembly. When the number the number three test cock is opened, water continues to flow and will not stop. What is the proper way to proceed? - Answers - Observe the reading on the gauge A booster pump is utilized to increase water pressure for the water user. When water pressure is increased within the internal water system to a higher pressure than the water suppliers pressure this creates: - Answers - Back pressure When testing a double check valve assembly, the test gauge and water in a sight tube must: - Answers - Remain at the same level The first recordable value a tester must obtain when testing a reduced pressure principle backflow prevention assembly is: - Answers - The relief valve opening point When conducting a test on a reduced pressure principle assembly, when flushing the kit in preparation for the test, the tester should close things in what order? - Answers - Close the #2 SOV, high side bleed and then the low side bleed Degree of hazard determines what? - Answers - What type of backflow assembly to install While conducting a test on a double check valve assembly, when the tester opens the test cock with the sight tube, the gauge stays at the upper end of the scale. What would this indicate? - Answers - The gauge and the sight tube have been incorrectly applied A tester has conducted a test on a reduced pressure principle assembly with the following results - relief valve opened at 3.2, #2 check held tight against backpressure and the #1 check held steady differential of 4.9. What does this indicate? - Answers - The assembly has failed the test The largest size of backflow prevention assemblies are: - Answers - 2" for pressure vacuum breakers, spill resistant vacuum breakers and 12" for double check valves and reduced pressure principle assemblies

A tester is conducting the second check test on a reduced pressure principle assembly and when the bypass control needle is opened, the gauge reading increases slightly. What must the tester do after seeing this? - Answers - Close the #2 test cock During the #1 check test on a double check valve assembly when the #3 test cock is opened, the water in the sight tube recedes. What would this indicate and what should the test do next? - Answers - The #2 check is faulty and the #2 shut off valve is leaking by. The tester should stop the test and fail the assembly Supply water pressure on a reduced pressure principle closes the relief valve. What causes the check valve on a pressure vacuum breaker to close? - Answers - The check spring The #1 check valve in the double check assembly is loaded to 1 PSI or greater, the # check of the Reduced Pressure Principle Assembly is loaded to? - Answers - 5.0 PSI or greater While conducting the first test on a pressure vacuum breaker, the tester finds the # shut off valve is leaking by. After following procedure of opening the #1 test cock and reopening the high bleed 1/4 turn, the air inlet still will not open and water continues to flow. What should the tester do next? - Answers - Fail the air inlet and move to the check test The pressure loss across a reduced pressure principle assembly is what depending on the size of the assembly? - Answers - 13 to 24 PSI Test cock #1 on a reduced pressure principle assembly can be utilized to gain passing test results if the assembly has; - Answers - A slightly leaking #2 SOV with usage On a type 2 Double Check Detector Assembly the test procedures should be done in what manner? - Answers - The bypass check, the main #1 check valve and then the # check A barometric loop containing potable water from a water distribution system must be how high at a minimum? - Answers - 35 feet A proper air gap is defined as: - Answers - Two times the diameter of the supply pipe above the flood rim of the receiving vessel and never less than 1 inch When a water supply enters a Spill Resistant Vacuum Breaker Assembly the water; - Answers - Passes through the open #1 SOV, closes the air inlet, opens the check valve and proceeds through the open #2 shut off valve Flushing the relief valve of a reduced pressure principle assembly can be achieved by - Answers - Closing both #1 and #2 SOV's and open the #2 test cock