A set of practice questions and answers related to the pjm (pennsylvania-new jersey-maryland) generation dispatcher exam. It covers various aspects of power system operation, including voltage regulation, generator limits, synchronization, emergency procedures, and reactive power management. The questions address real-time operating scenarios, nerc disturbance reporting, and market operations within the pjm system. This resource is valuable for individuals preparing for the pjm generation dispatcher exam, offering insights into the practical knowledge required for grid operation and emergency response. It also touches on topics such as black start procedures, frequency control, and maintenance outages, providing a comprehensive overview of the dispatcher's responsibilities. Designed to test and reinforce understanding of critical concepts in power system management and grid stability, making it an essential study aid for aspiring dispatchers.

Typology: Exams

2024/2025

Available from 06/21/2025

Lectjoshua
Lectjoshua 🇺🇸

4.5

(9)

24K documents

1 / 8

Toggle sidebar

This page cannot be seen from the preview

Don't miss anything!

bg1
PJM Generation Dispatcher Exam Practice
Questions with correct answers
An |EXCITER |on |a |traditional |generator |does |what? |- |CORRECT |ANSWER✔✔-Voltage |regulation |
(AVR) |if |you |change |the |excitation |current, |you |change |the |voltage.
ECO |Min, |ECO |Max, |and |EMERG |Max |are |genrator |_________________. |- |CORRECT |
ANSWER✔✔-Limits
When |synchronizing |to |the |interconnection, |what |needs |to |be |synchronized? |- |CORRECT |
ANSWER✔✔-Frequency, |Voltage, |and |phase |angle.
GMD |(GeoMagnetic |Disturbance) |procedure |is |implemented |when? |- |CORRECT |ANSWER✔✔-
10A |or |greater |is |measured |by |special |equipment |at |Missouri |Ave |or |Meadowbrook |and |the |
measurement |is |confirmed |by |one |of |the |following |other |sources: |Excess |transformer |current |
@ |Meadowbrook, |Beddington, |Donbs, |or |Black |Oak, |high |MVAR |requirements |on |transformers
|@ |Hopw |Creek |or |Salem |nuclear |subs, |or |high |DC |measurements |@ |Limerick |or |Peach |
Bottom.
What |are |the |2 |types |of |National |Terrorism |Advisory |Alerts? |- |CORRECT |ANSWER✔✔-Elevated |
and |Imminent.
What |action |does |PJM |take |for |a |terrorist |attack, |fuel |delivery |emergency, |or |GMD's? |- |
CORRECT |ANSWER✔✔-Conservative |Operations
What |does |PJM |put |the |most |emphasis |on |during |a |terrorist/sabotage |event? |- |CORRECT |
ANSWER✔✔-Operations |and |Communications
pf3
pf4
pf5
pf8

Partial preview of the text

Download PJM Generation Dispatcher Exam Practice Questions and more Exams Nursing in PDF only on Docsity!

PJM Generation Dispatcher Exam Practice

Questions with correct answers

An |EXCITER |on |a |traditional |generator |does |what? |- |CORRECT |ANSWER✔✔-Voltage |regulation | (AVR) |if |you |change |the |excitation |current, |you |change |the |voltage. ECO |Min, |ECO |Max, |and |EMERG |Max |are |genrator |_________________. |- |CORRECT | ANSWER✔✔-Limits When |synchronizing |to |the |interconnection, |what |needs |to |be |synchronized? |- |CORRECT | ANSWER✔✔-Frequency, |Voltage, |and |phase |angle. GMD |(GeoMagnetic |Disturbance) |procedure |is |implemented |when? |- |CORRECT |ANSWER✔✔- 10A |or |greater |is |measured |by |special |equipment |at |Missouri |Ave |or |Meadowbrook |and |the | measurement |is |confirmed |by |one |of |the |following |other |sources: |Excess |transformer |current | @ |Meadowbrook, |Beddington, |Donbs, |or |Black |Oak, |high |MVAR |requirements |on |transformers |@ |Hopw |Creek |or |Salem |nuclear |subs, |or |high |DC |measurements |@ |Limerick |or |Peach | Bottom. What |are |the | 2 |types |of |National |Terrorism |Advisory |Alerts? |- |CORRECT |ANSWER✔✔-Elevated | and |Imminent. What |action |does |PJM |take |for |a |terrorist |attack, |fuel |delivery |emergency, |or |GMD's? |- | CORRECT |ANSWER✔✔-Conservative |Operations What |does |PJM |put |the |most |emphasis |on |during |a |terrorist/sabotage |event? |- |CORRECT | ANSWER✔✔-Operations |and |Communications

What |does |PJM |request |during |a |low |voltage |alert? |- |CORRECT |ANSWER✔✔-RRC |- |reactive | reserve |check PJM |issues |a |Heavy |Load |Voltage |Warning |how |many |hours |prior |to |implementation? |- | CORRECT |ANSWER✔✔-4 |hours What |should |generation |owners/operators |do |during |a |High |System |Voltage |Action? |- | CORRECT |ANSWER✔✔-Operate |at |the |lower |bandwidth |of |the |voltage |schedule. How |many |hours |do |you |have |to |report |a |24-hr |reportable |NERC |disturbance? |- |CORRECT | ANSWER✔✔-6 |hours What |report |is |generated |during |a |Max |Emergency |Gen |Alert? |- |CORRECT |ANSWER✔✔-SSR |- | Supplementary |Status |Report What |part |of |the |SSR |is |the |Fuel |Limited |Resources |accounted |for? |- |CORRECT |ANSWER✔✔- Part |G |Resource |Limited |Units |which |are |units |that |are |not |able |to |run |at |max |capacity |for | more |than | 72 |hours. What |kind |of |Emergency |Procedures |occur |during |real |time |operating |hours? |- |CORRECT | ANSWER✔✔-Actions What |is |the |per |Unit |(p.u.) |for |a | 345 |kV |nominal |voltage |that |is |currently |at | 348 |kV? |- | CORRECT |ANSWER✔✔-348/345 |= |1.008 |pu What |is |the |Emergency |Reducible |Generation |(ERG) |if |the |Eco |Min |is | 100 |and |the |Emergency | Min |is |75? |- |CORRECT |ANSWER✔✔-Eco |Min |- |Emerg |Min |= |25MW

What |size |generating |units |must |provide |instantaneous |power |and |reactive |flow |data? |- | CORRECT |ANSWER✔✔-10 |MW |and |above How |often |must |PJM |be |updated |for |manually |entered |data? |- |CORRECT |ANSWER✔✔-30 |min How |often |is |generator |reactive |capability |testing |required? |- |CORRECT |ANSWER✔✔-Every | 5 | yrs. How |much |notification |is |required |to |bring |a |self-scheduled |unit |online? |- |CORRECT | ANSWER✔✔-20 |min What |time |of |the |day |does |the |DA- |Day |ahead |market |close? |- |CORRECT |ANSWER✔✔-1200 | EST |and |all |bids |must |be |in |by |this |time. Eco |Min, |Eco |Max, |and |Emerg |max |are |all |generator |______________ |. |- |CORRECT | ANSWER✔✔-Limits What |time |is |the |rebidding |period |for |the |DA |market? |- |CORRECT |ANSWER✔✔-4 |- | 6 |pm Who |specifies |the |voltage/reactive |power |schedule? |- |CORRECT |ANSWER✔✔-TO |- | transmission |owner PJM |requires |generators |that |are |greater |than |what |level |to |follow |a |voltage |schedule? |- | CORRECT |ANSWER✔✔-20 |MVA |or |aggregated | 75 |MVA PJM |sends |what |signals |to |Market |Operation |Centers? |- |CORRECT |ANSWER✔✔-ACE, | Regulation, |and |Dispatch

PJM |instructs |your |Generator |to |come |online. |From |what |time |to |the |time |it |is |running? |- | CORRECT |ANSWER✔✔-Notification |time |+ |Time |to |start Operating |reserves |consists |of |what? |- |CORRECT |ANSWER✔✔-Synchronized |reserves, |non- synchronized |reserves |(quick |start), |and |supplemental |reserves |(secondary) Regulating |units |(demand |response |resources) |provide |a |variable |amount |of |generation |under | automatic |control |to |provide |what? |- |CORRECT |ANSWER✔✔-Correction |for |small |deviations |in |load. Where's |the |ideal |point |for |regulation |to |operate? |- |CORRECT |ANSWER✔✔-Midpoint What |type |of |outage |may |be |deferred |to |beyond |the |next |weekend |or |can |be |postponed |to | the |following |Mon |morning |at |0800? |- |CORRECT |ANSWER✔✔-Maintenance |outage How |long |is |a |maintenance |outage |during |PPM- |Peak |Period |Maintenance? |- |CORRECT | ANSWER✔✔-9 |days How |long |is |a |maintenance |outage |during |non-Peak |Period |Maintenance? |- |CORRECT | ANSWER✔✔-Unlimited When |ambient |temperatures |are |low, |what |happens |to |CT |operation? |- |CORRECT | ANSWER✔✔-MW |increased |as |temperature |decreases. What |is |the |maximum |amount |of |reactive |power |increments |put |onto |the |grid |during |a | reactive |power |capability |test |at |one |time? |- |CORRECT |ANSWER✔✔-100 |MVAR

During |restoration |what |is |the |frequency |control |range? |- |CORRECT |ANSWER✔✔-59.75 |- |61.0 | Hz What |permits |the |manual |closing |of |a |circuit |breaker |between | 2 |control |areas? |- |CORRECT | ANSWER✔✔-Synchroscope What |is |the |normal |frequency |control |mode |used |by |PJM? |- |CORRECT |ANSWER✔✔-Tie-line | bias A |unit |running |for |transmission |congestion |is |subject |to |what? |- |CORRECT |ANSWER✔✔-Price | cost |capping What |kind |of |transformers |are |used |to |measure |power |line |voltages? |- |CORRECT |ANSWER✔✔- Potential |Transformers What |is |the |lowest |voltage |in |the |BES? |- |CORRECT |ANSWER✔✔-100 |kV What |is |the |lowest |operating |voltage |in |PJM? |- |CORRECT |ANSWER✔✔-115 |kV What |side |of |the |transformer |is |connected |to |the |power |source? |- |CORRECT |ANSWER✔✔- Primary |winding If |a |generator |is |under |excited, |(-) |value, |absorbing |VAR's |is |it |leading |or |lagging? |- |CORRECT | ANSWER✔✔-Leading

PJM |calls |and |instructs |you |to |increase |MVAR |output |for |voltage |support |by | 50 |MVAR. |What | do |you |do? |- |CORRECT |ANSWER✔✔-Look |at |"D" |curve |and |decrease |your |MW |output |to |a | level |that |will |increase |reactive |power |output |by | 50 |MVAR. Planned |outages |are |submitted |no |later |than? |- |CORRECT |ANSWER✔✔-30 |days