SIS SIS
SIS
SIS
SIS
SIS SIS
SIS
SIS SIS
DORM.
SALA
COZINHA
BANHO
DORM. 2
DORM. 1
SALA
COZINHA
TERRAÇO COB.
TERRAÇO
COBERTO
GUARDA-CORPO H=1,20m
UNIDADE
FINAL 02
UNIDADE
FINAL 03
UNIDADE
FINAL 04
UNIDADE
FINAL 05
UNIDADE
FINAL 07
UNIDADE
FINAL 08
UNIDADE
FINAL 09
UNIDADE
FINAL 01
UNIDADE
FINAL 06
DORM.
SALA
COZINHA
TERRAÇO COBERTO
GUARDA-CORPO H=1,20m
UNIDADE
FINAL 10
VAZIO
VARIÁVEL
28.55m²
BOX (opção 3 - 0.70x0.90 mín)
3.26m²
34.16m²
2.81m²
3.26m²
3.26m²
BOX (opção 2 - 0.70x0.90 mín)
3.26m²
3.26m²
BOX (opção 2 - 0.70x0.90 mín)
3.26m²
27.27m²
BOX (opção 2 - 0.70x0.90 mín)
3
2
1
45
C
QLT-TIPO
5
4
1
32
a
a
a
b
b
c
c
d
d,e,f
f
e
e
g
g
h
h
C
QLT-TIPO
AC
AC
a
a
bb
cd
e
f
c,d,e
g
g
a
4
f
AC
C
QLT-TIPO
3
2
1
5
a
a
b
b
c,d,e ed
c
ff
g
g
BARRAMENTO
BLINDADO BUSWAY
CAIXA MEC XII
DIM.: 1,62x1,00x0,25 m
QLT-TIPO
QLT-TIPO
QLT-TIPO
QLT-TIPO
PRUMADA
DE SISTEMAS
ELETROCALHA LISA C/ TAMPA
DIM.:150x50mm
ALIMENTADORES DA ADM
QLT
TIPO
VER DET. 001
SIS
SIS
SIS
SIS
Ø1"
SIS
SIS
QLT-TIPO QLT
TIPO
Ø1"
QLT-TIPO
QLT
TIPO
SIS
SIS
Ø1"
SIS
SIS
QLT-TIPO
QLT
TIPO
Ø1"
VER DET. 001
SIS
QLT
TIPO Ø1"
QLT
TIPO
Ø1"
QLT
TIPO
SIS
Ø1"
QLT
TIPO
VER DET. 001
SIS
Ø1" Ø1"
SIS SIS SIS SIS SIS SIS SIS SIS
SIS
INT
INT INT INT INT INT INT
QLT
TIPO
QLT
TIPO
ELETROCALHA LISA C/ TAMPA - 200x50mm
ALIMENTADORES DAS UNIDADES PRIVATIVAS
ELETROCALHA LISA C/ TAMPA - 150x50mm
SISTEMAS
ELETROCALHA LISA C/ TAMPA - 200x50mm
ALIMENTADORES DAS UNIDADES PRIVATIVAS
ELETROCALHA LISA C/ TAMPA - 150x50mm
SISTEMAS
DETALHE
SEM ESCALA
FIXAÇÃO E PASSAGEM DA ELETROCALHA E ELETRODUTOS
1
2 3
1
2
3
ESTRUTURA DE FIXAÇÃO COM VERGALHÃO, BRAÇADEIRA ZZ E PERFILADO
38x38, VER DETALHE ESPECÍFICO NO PROJETO DE ELÉTRICA.
ELETROCALHA LISA DIM.:150mm x 50mm - COM TAMPA - SISTEMAS.
ELETROCALHA LISA DIM.:200mm x 50mm - COM TAMPA - PARA
ALIMENTAÇÃO ENERGIA DAS UNIDADES PRIVATIVAS.
PISO
LAJE
4 1
73
2
35
6
9
8
FORRO
DETALHE 001
DERIVAÇÃO EMBUTIDO PARA APARENTE
SEM ESCALA
1 ELETRODUTO Ø1" EMBUTIDO NA LAJE (SEGUE PARA APTO)
2 ELETRODUTO SEAL TUBE Ø1.1/4" (ELÉTRICA) OU Ø1" (SISTEMAS)
3 CONECTOR CMRA PARA SEAL TUBE Ø1.1/4" OU Ø1"
5 SAÍDA HORIZONTAL PARA ELETRODUTO Ø1.1/4" OU Ø1"
8 FIXAÇÃO DA ELETROCALHA NA ESTRUTURA DE FIXAÇÃO
9 PERFILADO PARA FIXAÇÃO DA ELETROCALHA, VER DET. ESPECÍFICO
6 ELETROCALHA LISA COM TAMPA, DE ALIMENTADORES OU SISTEMAS
DIMENSÕES VER PLANTA
7 CAIXA DE PASSAGEM 100 x 100mm COM FUNDO FALSO PARA DERIVAÇÃO
APARENTE / EMBUTIDO
4 CAIXA OCTOGONAL EMBUTIDA NA LAJE (UTILIZAR SERRA COPO PARA INSTALAR
ELETRODUTO 1.1/4")
PISO
LAJE
FORRO
0.27 0.27
ITEM COMENTÁRIO
01 ABSORVER SEPARAÇÃO NOS SHAFTS DE ELÉTRICA CONFORME INDICADO EM PLANTA.
02 VALIDAR POSSIBILIDADE DE INVERSÃO DA PIA E CHURRASQUEIRA, CONFORME SOLICITADO PELA HIDRÁULICA.
03 DESLOCAR PORTA 5cm PARA VIABILIZAR A INSTALAÇÃO DO ACIONADOR DA CAMPAINHA.
04 DEVIDO A GRANDE QUANTIDADE DE UNIDADES POR PAVIMENTO E A LOCAÇÃO DOS SHAFTS ESTAMOS PREVENDO QUE A
ALIMENTAÇÃO DAS UNIDADES SEJA REALIZADA ATRAVÉS DE ELETROCALHA.
05
VALIDAR LOCAÇÃO DE PONTOS E CARGAS NAS UNIDADES PRIVATIVAS:
1
1
2
2
2
2
2
2
2
QD-FOL-A0
PLANTA BAIXA - 2º AO 8º PAVIMENTO - TIPO 01
INSTALAÇÕES ELÉTRICAS
ESC.: 1:50
FOLHA A0 - Dimensões: 841mm x 1189mm
A cópia ou utilização sem a prévia autorização da Office Engenharia constitui em crime.
NOME DO ARQUIVO
COORDENADOR
REVISÃO
CREA
PROJETISTA
RESPONSÁVEL DO PROJETO
SUB DISCIPLINA
REPRESENTADO NESTA PRANCHA
ENDEREÇO
FOLHA
ESCALA
PROJETO
RESIDENCIAL TIMBIRAS
DESCRIÇÃO:
REVISÃO: DATA: EMITIDO POR:
NÚMERO ART
ETAPA
DATA DE EMISSÃO
RUA RIACHUELO, 837, PAVIMENTO SUPERIOR, CENTRO | STA BÁRBARA D'OESTE-SP | CEP 13450-020 | TEL.:19 9.9675-7415
RUA DOS TIMBIRAS X RUA DOS BOTICÁRIOS
SÃO PAULO - SP
INSTALAÇÕES ELÉTRICAS
ESTUDO PRELIMINAR
MAICON R. BATISTA
ROGÉRIO CASAGRANDEVANESSA MELO
002
2º AO 8º PAVIMENTO
ALIMENTADORES E SISTEMAS
SNZ06RSC-ELE-EP-002-TIP-PLA-R00
1:50
17/02/2024
R00
R00 17/02/2024 EMISSÃO INICIALVANESSA
507.019.559-0
SNZ06RSC-ARQ-EP-003-TIP-PLA-R01
PLANTA BAIXA 1º PAVIMENTO E TIPO 1 - 2º AO 8º PAVIMENTO
R01 07/11/2023Arquitetura
REFERÊNCIA ASSUNTO ARQUIVO REV DATA
PONTO DE TV - EM CX. 4"X2" - EMBUTIDO - H= 0,30M OU INDICADA
PONTO DE INTERFONE - EM CX. 4"X2" - EMBUTIDO - H= 1,10M OU INDICADA
DESCRIÇÃO DO SÍMBOLO - SISTEMAS
SÍMBOLO
PONTO PARA ILUMINAÇÃO COM CAIXA OCTOGONAL EMBUTIDA NO TETO
DESCRIÇÃO DO SÍMBOLO - ILUMINAÇÃO
SÍMBOLO
CJ. 1 INTERRUPTOR UNIP. SIMPLES E 1 TOMADA 127V 2P+T-20A EM CX. 4"X2" - EMBUTIDO
H= 1,10M OU INDICADA
TOMADA PADRÃO BRASILEIRO CONFORME NORMA ABNT NBR 14136; 250V.
DESCRIÇÃO DO SÍMBOLO - CONJUNTOS
SÍMBOLO
TOMADA 220V 2P+T-20A EM CX. 4"X2" - EMBUTIDA - H= 1,10M OU INDICADA
CJ. 2 TOMADAS - 127V 2P+T-20A EM CX. 4"X2" - EMBUTIDO - H= 1,10M OU INDICADA
TOMADA 127V 2P+T-20A EM CX. 4"X2" - EMBUTIDA - H= 1,10M OU INDICADA
TOMADA 127V 2P+T-20A EM CX. 4"X2" - EMBUTIDA - H= 0,30M OU INDICADA
TOMADA 127V 2P+T-20A EM CX. 4"X2" - EMBUTIDA - H= 2,20M OU INDICADA
CJ. 2 TOMADAS - 127V 2P+T-10A EM CX. 4"X2" - EMBUTIDO - H= 0,30M OU INDICADA
TOMADA 127V 2P+T-10A EM CX. 4"X2" - EMBUTIDA - H= 0,30M OU INDICADA
TOMADA PADRÃO BRASILEIRO CONFORME NORMA ABNT NBR 14136; 250V.
DESCRIÇÃO DO SÍMBOLO - TOMADAS
SÍMBOLO
INTERRUPTOR UNIP. SIMPLES EM CX. 4"X2" - EMBUTIDO - H= 1,10M OU INDICADA
INTERRUPTOR UNIP. PARALELO EM CX. 4"X2" - EMBUTIDO - H= 1,10M OU INDICADA
CJ. 3 INTERRUPTORES UNIP. SIMPLES EM CX. 4"X2" - EMBUTIDO - H= 1,10M OU INDICADA
CJ. 2 INTERRUPTORES UNIP. SIMPLES E 1 UNIP. PARALELO EM CX. 4"X2" - EMBUTIDO
H= 1,10M OU INDICADA
ACIONADOR CAMPAINHA EM CX. 4"X2" - EMBUTIDO - H= 1,10M OU INDICADA
C
DESCRIÇÃO DO SÍMBOLO - INTERRUPTORES
SÍMBOLO
CIGARRA DE CAMPAINHA EM CX. 4"X2" - EMBUTIDO - H= 2,20M OU INDICADA
PONTO DE FORÇA PARA AR CONDICIONADO - INSTALADO JUNTO AO EQUIPAMENTO
AC
DESCRIÇÃO DO SÍMBOLO - FORÇA
SÍMBOLO
CJ. 1 PONTO DE TELEFONE E PONTO DE TV - EM CX. E 4"x4" - EMBUTIDO - H= 0,30M OU INDICADA
ELETRODUTO APARENTE DE ELÉTRICA
ELETRODUTO EMBUTIDO (TETO/PAREDE) DE ELÉTRICA
ELETRODUTO EMBUTIDO (PISO) DE ELÉTRICA
INT ELETRODUTO APARENTE DE INTERFONE
INT ELETRODUTO EMBUTIDO (TETO/PAREDE) DE INTERFONE
INT ELETRODUTO EMBUTIDO (PISO) DE INTERFONE
SIS ELETRODUTO APARENTE DE SISTEMAS
SIS ELETRODUTO EMBUTIDO (TETO/PAREDE) DE SISTEMAS
SIS ELETRODUTO EMBUTIDO (PISO) DE SISTEMAS
- RÍGIDOS EM INSTALAÇÕES APARENTES.
- FLEXÍVEL CORRUGADO TIPO A CLASSE MÉDIA PARA DRYWALL.
- FLEXÍVEL CORRUGADO TIPO A CLASSE LEVE PARA ALVENARIA.
- FLEXÍVEL LISO TIPO B CLASSE MÉDIA PARA LAJES.
REQUISITOS PARA ELETRODUTOS DE ACORDO NBR 15465.
DESCRIÇÃO
TUBULAÇÃO
INDICAÇÃO DE PRUMADA QUE PASSA
INDICAÇÃO DE PRUMADA QUE DESCE OU SUBIDA
INDICAÇÃO DE ELETRODUTO QUE SOBE
INDICAÇÃO DE ELETRODUTO QUE PASSA
INDICAÇÃO DE ELETRODUTO QUE DESCE
INDICAÇÃO DE SINALIZAÇÃO/COMANDO - VER ESQUEMA VERTICAL
.
INDICAÇÃO DO CIRCUITO ALIMENTADOR - VER DIAGRAMAS
DESCRIÇÃO DO SÍMBOLO - DIVERSOS
SÍMBOLO
DESCRIÇÃO DA LEGENDA - PONTOS DE USO ESPECÍFICO
LEGENDA
NBR-13897, NBR13898 E NBR-15465, QUANDO NÃO INDICADO A SEÇÃO DEVERÁ SER -110mm. (CASO APLICÁVEL)
7 - ALIMENTADORES ENTERRADOS DEVERÃO UTILIZAR ELETRODUTO FLEXÍVEL CORRUGADO EM PEAD, CONFORME:
DEVENDO POSSUIR CAIXAS DE TOMADA PARA CADA LUMINÁRIA (CASO APLICÁVEL)
6 - OS PERFILADOS E ACESSÓRIOS, DEVERÃO SER DO TIPO LISO COM TAMPA, ZINCADO, CHAPA #14MSG,
ZINCADAS, CHAPA#16MSG, COM AS SEÇÕES INDICADAS EM PROJETO.(CASO APLICÁVEL)
5 - AS ELETROCALHAS, COM SEUS RESPECTIVOS ACESSÓRIOS E CONEXÕES, DEVERÃO SER DO TIPO LISA C/ TAMPA,
4 - TUBULAÇÃO NÃO COTADA Ø3/4".
3 - PARA ESPECIFICAÇÃO COMPLETA DOS MATERIAIS, VER MEMORIAL DESCRITIVO.
2 - OS DETALHES CONSTRUTIVOS DEVEM OBSERVAR O PROJETO DE ARQUITETURA.
1 - ESTE PROJETO FOI ELABORADO EM CONFORMIDADE, COM A NBR 5410
NOTAS
O PROJETO ATENDE AOS REQUISITOS DAS SEGUINTES NORMAS:
ABNT NBR 5419-1/2015 PROTEÇÃO CONTRA DESCARGAS ATMOSFÉRCAS - PARTE 1: PRINCÍPIOS GERAIS.
ABNT NBR 5419-2/2015 PROTEÇÃO CONTRA DESCARGAS ATMOSFÉRCAS - PARTE 2: GERENCIAMENTO DE RISCO.
ABNT NBR 5419-3/2015 PROTEÇÃO CONTRA DESCARGAS ATMOSFÉRCAS - PARTE 3: DANOS FÍSICOS A ESTRUTURAS E PERIGOS À VIDA.
ABNT NBR 5419-4/2015
ABNT NBR 5410/2004 INSTALAÇÕES ELÉTRICAS DE BAIXA TENSÃO.
ABNT NBR 17240/2010
SISTEMA DE ILUMINAÇÃO DE EMERGÊNCIA
ABNT NBR 10898/2023
MANUAIS E DIRETRIZES DAS CONCESSIONÁRIAS DE ENERGIA ELÉTRICA E TELECOMUNICAÇÃO DO MUNÍCIPIO.
-
-
-
-
-
-
-
-PROTEÇÃO CONTRA DESCARGAS ATMOSFÉRCAS - PARTE 4: SISTEMAS ELÉTRICOS E ELETRÔNICOS INTERNOS
NA ESTRUTURA
SISTEMA DE DETECÇÃO E ALARME DE INCÊNDIO - PROJETO, INSTALAÇÃO, COMISSIONAMENTO E MANUTENÇÃO
DE SISTEMAS DE DETECÇÃO E ALARME DE INCÊNDIO - REQUISITOS
ABNT NBR 15575/2021 EDIFICAÇÕES HABITACIONAIS - DESEMPENHO.
-
8 - PONTOS INSTALADOS EM PAREDES QUE REQUEREM TRRF 120MIN, DEVERÃO RECEBER MASSA CORTA FOGO.
1
3
4
2
TOMADA 127V 2P+T-10A EM CX. 4"X2" - EMBUTIDA - H= 1,90M - DEPURADOR
TOMADA 127V 2P+T-10A EM CX. 4"X2" - EMBUTIDA - H= 0,70M - FOGÃO A GÁS
TOMADA 127V 2P+T-20A EM CX. 4"X2" - EMBUTIDA - H= 1,50M - MICROONDAS
5TOMADA 220V 2P+T-20A EM CX. 4"X2" - EMBUTIDA - H= 0,70M - M.L.R.
CJ. 2 TOMADAS - 127V 2P+T-20A EM CX. 4"X2" - EMBUTIDO - H= 1,10M - AQUECEDOR À GÁS